Mounting directly on the fl oor.
1) Fix the leg of indoor unit on the fl oor with 2 mounting screws.
2) Fix the upper part of indoor unit on the wall with 4 mounting screws.
(Floor installation)
6 screw
(M4 x 25L)
NOTE
• In case the plinth is fi xed to the wall, please make sure to cut out the slit
on the left and right side of the main part.
Installation on the wall
1) Fix the installation plate on the wall with 4 mounting screws.
2) Hook the indoor unit on the installation plate.
3) Fix the upper part of indoor unit on the wall with 4 mounting screws.
(Wall installation)
4 screw
(M4 x 25L)
4 screw
(M4 x 25L)
CAUTION
Make sure to fi x it at a designated position with the screws.
Failure may result the damage of piping by the turning over of a set.

Concealed Installation

The special method to install the indoor unit bury in the wall is shown here.
Please make sure to change to wall burying mode.
1. To switch to the wall burying mode
To switch to the wall burying mode, press and hold AIR OUTLET
SELECT button for 20 seconds.
- When the operation set up and 5 beep sounds. Then indication at
Temperature indicator will light up for 5 seconds.
- To cancel, press AIR OUTLET SELECT button for 20 seconds then, 5
beep sounds. Then indication at Temperature indicator will blinks for 5
seconds.
- To prevent dewfall, above plate angle should be narrow.
Slit
2. Wall hole size
Wall hole size should be enough to keep the distance with indoor unit as
shown in the following fi gure.
(Front view)
Cut dot-line area
Floor
50 or more
3. Installation using the supporting plate
• To install into the existing wall hole, if it is impossible to keep 20-30 mm
of depth, use the supporting plate for securing the distance.
• Arrange the screw positions and supporting plate as shown in the
fi gure.
• Be sure to switch to wall burying mode.
(Rear screws potion)
4. In case of lattice establishment
• Follow the following fi gure, make sure to keep enough distance
between lattice, frame and wall.
• Be sure to switch to wall burying mode.
• The lattice should be make of wood.
• Between the air inlet and outlet, should be devided with partition board.
• Be sure to establish the open part for RECEIVER.
• The open part of lattice must be opens 70 % or more of the wall hole.
• The open part of lattice must be arranged uniformly.
(Top view)
6
Wall burying mode
(Unit : mm)
70 or more
800 or more
(700)
Indoor unit
50 or more
(Field supply)
670
: Screw holes
Partition board
For prevent dewfall
(Side view)
240 to 250
20 to 30
Floor
(Side view)
(Unit : mm)
(Unit : mm)