Toshiba Carrier MMD-AP0154SPH2UL Manual de instalación - Página 20

Navegue en línea o descargue pdf Manual de instalación para Aire acondicionado Toshiba Carrier MMD-AP0154SPH2UL. Toshiba Carrier MMD-AP0154SPH2UL 44 páginas. Air conditioner multi type

Check codes and parts to be checked
Check method
On the remote control (Wired remote control, Central control remote control) and the interface P.C. board of the
outdoor unit (I/F), a check display LCD (Remote control) or 7-segment display (on the outdoor interface P.C. board)
to display the operation is provided. Therefore the operation status can be known. With this self-diagnosis function,
a trouble or position with error of the air conditioner can be found as shown in the table below.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• To check from indoor remote control: See "Wired remote control display" in the list.
• To check from outdoor unit: See "Outdoor 7-segment display" in the list.
• To check from indoor unit with a wireless remote control: See "Sensor block display of receiving unit" in the list.
Check code
Wireless remote control
Sensor block display of
Outdoor 7-segment display
Wired remote
control display
Auxiliary code
Operation Timer Ready Flash
E01
E02
E03
E04
No. of indoor units in which
E06
E06
sensor has been normally
received
E07
E08
E08 Duplicated indoor addresses
E09
E10
01: Indoor / Outdoor
communication
E12
E12
02: Communication between
outdoor units
E15
E15
E16 00: Capacity over
E16
01 ~:No. of connected units
E18
00: Header is nothing
E19
E19
02: Two or more header units
01: Outdoor of other line
E20
E20
connected
02: Indoor of other line connected
E23
E23
E25
E25
No. of outdoor units which
E26
E26
received signal normally
E28
E28 Detected outdoor unit number
37-EN
IPDU : Intelligent Power Drive Unit
: Lighting,
: Flashing,
: Goes off
ALT : Flashing is alternately when there are two flashing LED.
SIM : Simultaneous flashing when there are two flashing LED.
Check code name
receiving unit
Communication error between indoor and remote
control
(Detected at remote control side)
Remote control transmission error
Communication error between indoor and remote
control (Detected at indoor side)
Communication circuit error between indoor /
outdoor (Detected at indoor side)
Decrease of No. of indoor units
Communication circuit error between indoor /
outdoor (Detected at outdoor side)
Duplicated indoor addresses
Duplicated header remote controls
Communication error between indoor MCU
Automatic address start error
Indoor is nothing during automatic addressing
Capacity over / No. of connected indoor units
Combined capacity of indoor units exceeds 120 %
of combined capacity of outdoor units.
Communication error between indoor units
Outdoor header units quantity error
Other line connected during automatic address
Sending error in communication between outdoor
units
Duplicated follower outdoor addresses
Decrease of No. of connected outdoor units
Follower outdoor unit error
– 19 –
Check code
Outdoor 7-segment display
Wired remote
control display
Auxiliary code
01
02
03
04
05
06
07
E31
E31
08
09
0A
0B
0C
0D
0E
Judging device
0F
: IPDU error
Remote control
F01
Remote control
F02
F03
Indoor
F04
F04
Indoor
F05
F05
TE1 sensor
F06
F06
I/F
TE2 sensor
F07
F07
I/F
F08
F08
F10
Indoor / I/F
F12
F12
Remote control
01: Comp. 1 side
Indoor
F13
F13
02: Comp. 2 side
03: Comp. 3 side
I/F
F15
F15
F16
F16
I/F
F22
F22
F23
F23
I/F
F24
F24
Indoor
F29
F31
F31
I/F
01: Comp. 1 side
H01
H01
02: Comp. 2 side
I/F
03: Comp. 3 side
01: Comp. 1 side
H02
H02
02: Comp. 2 side
I/F
03: Comp. 3 side
I/F
01: Comp. 1 side
H03
H03
02: Comp. 2 side
I/F
03: Comp. 3 side
H05
H05
I/F
H06
H06
H07
H07
01: TK1 sensor error
02: TK2 sensor error
H08
H08
03: TK3 sensor error
04: TK4 sensor error
H15
H15
Wireless remote control
Sensor block display of
Check code name
receiving unit
Operation Timer Ready Flash
A3-IPDU
Fan
IPDU
1
2
3
IPDU communication error
ALT Indoor TCJ sensor error
ALT Indoor TC2 sensor error
ALT Indoor TC1 sensor error
ALT TD1 sensor error
ALT TD2 sensor error
TE1 sensor error
ALT
TE2 sensor error
ALT TL sensor error
ALT TO sensor error
ALT Indoor TA sensor error
ALT TS1 sensor error
ALT TH sensor error
ALT Outdoor temp. sensor miswiring (TE1, TL)
ALT Outdoor pressure sensor miswiring (Pd, Ps)
ALT TD3 error
ALT Ps sensor error
ALT Pd sensor error
SIM Indoor other error
SIM Indoor EEPROM error
Compressor break down
Compressor trouble (lock)
Current detect circuit system error
TD1 miswiring
Low pressure protective operation
Oil level down detective protection
Oil level detective temp sensor error
TD2 miswiring
Judging device
I/F
Indoor
Indoor
Indoor
I/F
I/F
I/F
I/F
I/F
Indoor
I/F
IPDU
I/F
I/F
I/F
I/F
I/F
Indoor
I/F
IPDU
IPDU
IPDU
I/F
I/F
I/F
I/F
I/F
38-EN