Dimplex LI MS Datos técnicos - Página 3
Navegue en línea o descargue pdf Datos técnicos para Bomba de calor Dimplex LI MS. Dimplex LI MS 4 páginas. Indoor air source heat pumps
TECHNICAL DATA
EQUIPMENT DATA for air source heat pumps for heating purposes
1
TYPE AND COMMERCIAL DESCRIPTIONS
2
MODEL
2.1
Enclosure type acc to EN 60 529 for compact unit or heating element IP 21
2.2
Installation site
3
PERFORMANCE DATA
3.1
Operating temperature limits:
Heating water supply / return
Air
3.2
Heating water temperature difference at A2 / W35
3.3
Heating capacity/coeff.of perform.
3.4
Sound power level of unit / outside
3.5
Heating water flow rate at internal pressure difference
3.6
Air flow rate at external static pressure difference
3.7
Refrigerant: total charge weight
4
DIMENSIONS, CONNECTIONS AND WEIGHT
4.1
Equipment dimensions
4.2
Equipment connections for heating system
4.3
Air duct inlet and outlet (min. inside dimensions)
4.4
Weight of transport unit(s) incl. packaging
5
ELECTRICAL CONNECTIONS
5.1
Nominal voltage; fusing
5.2
Nominal power consumption
5.3
Starting current with soft starter
5.4
Nominal current A2 W35/cos
6
COMPLIES WITH EUROPEAN SAFETY REGULATIONS
7
OTHER DESIGN CHARACTERISTICS
7.1
Defrosting
Type of defrosting
Defrost pan available
7.2
Heating water inside unit protected against freezing
7.3
Performance settings
7.4
Controller internal / external
1)
This data characterises the size and performance capacity of the system. For economic and energy consumption reasons, additional factors such as
defrosting behaviour, bivalence point and control need to be taken into consideration. Abbreviations have the following meaning e.g. A2 / W55: heat source
temperature 2°C and heating water supply temperature 55°C.
2)
The heat circulating pump and the controller of the heat pump must be on standby at all times.
3)
See operating limits diagram.
See CE Declaration of Comformity.
4)
Subject to technical modifications
3)
at A-7 / W35
1)
at A2 / W35
1)
at A2 / W50
1)
at A7 / W35
1)
at A10 / W35
1)
1)
A2 W35
2)
°C / °C
Max. 55 / min. 18
°C
kW/---
kW/---
kW/---
kW/---
kW/---
dB(A)
m
3
/h/Pa
m
3
/h/Pa
m
3
/h/Pa
Type / kg
R404A / 2.5
H x W x L mm
1360 x 750 x 850
inches
G 1" ext. thread
L x W mm
kg
V/A
kW
A
A /---
Cycle reversal
Yes (heated)
LI11MS
IP 21
Indoors
Max. 55 / min. 18
-20 to +35
7.5
7.6 / 2.9
9.1 / 3.4
9.0 / 2.5
10.9 / 4.1
12.0 / 4.6
55 / 61
1.0 / 3000
4200 / 0
2500 / 25
1570 x 750 x 850
G 1" ext. thread
500 x 500
200
230 / 25
2.65
38
14.4 / 0.8
4)
Automatic
Yes
1
External
LI16AS
IP 21
Indoors
-20 to +35
7.5
9.8 / 2.6
12.2 / 3.2
11.5 / 2.4
15.4 / 3.7
16.1 / 3.8
57 / 62
1.4 / 4500
5200 / 0
4000 / 25
R404A / 3.1
570 x 570
235
400 / 20
3.81
25
6.9 / 0.8
4)
Automatic
Cycle reversal
Yes (heated)
Yes
1
External