Whirlpool 3LWED4830FW Manual de instrucciones de instalación - Página 12

Navegue en línea o descargue pdf Manual de instrucciones de instalación para Secadora Whirlpool 3LWED4830FW. Whirlpool 3LWED4830FW 19 páginas. 737 mm (29 inch) wide models – gas & electric

Whirlpool 3LWED4830FW Manual de instrucciones de instalación
Alternate installations for close clearances
Venting systems come in many varieties. Select the type best
for your installation. Two close-clearance installations are shown.
Refer to the manufacturer's instructions.
Over-The-Top installation (also available with one offset elbow)
Periscope installation
NOTE: The following kits for close clearance alternate
installations are available for purchase.

Venting Kits

For more information, visit us at www.applianceaccessories.com
or contact the dealer from whom you purchased your dryer or an
authorized service company.
Part Number Descriptions
8171587RP
0–5" Metal vent periscope
4396037RP
0"–18" Metal vent periscope
4396011RP
18"–29" Metal vent periscope
4396014
29"–50" Metal vent periscope
4392892
In-Wall metal DuraVent™ Periscope
4396028
Sure Connect™ venting kit
(over-the-top installation)
4396009RP
5' Universal connect vent, flexible dryer venting
4396010RP
6' SecureConnect™ vent, flexible dryer venting
4396013RB
Dryer vent installer's kit
4396033RP
5' flexible dryer venting with clamps
4396727RP
8' flexible dryer venting with clamps
4396004
Dryer offset elbow
4396005
Wall offset elbow
4396006RW
DuraSafe™ close elbow
4396007RW
Through-the-wall vent cap
4396008RP
4" steel dryer venting clamps – 2 pack
8212662
Flush-mounting louvered vent hood 4"
12
Special provisions for mobile home installations:
The exhaust vent must be securely fastened to a noncombustible
portion of the mobile home structure and must not terminate
beneath the mobile home. Terminate the exhaust vent outside.
Determine vent path:
Select route that will provide straightest and most direct path
n
outdoors.
Plan installation to use fewest number of elbows and turns.
n
When using elbows or making turns, allow as much room
n
as possible.
Bend vent gradually to avoid kinking.
n
Use as few 90° turns as possible.
n
Determine vent length and elbows needed for best
drying performance:
Use following "Vent System Chart" to determine type of vent
n
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specified
in "Vent System Chart." Exhaust systems longer than those
specified will:
Shorten life of dryer.
n
Reduce performance, resulting in longer drying times and
n
increased energy usage.
The "Vent System Chart" provides venting requirements that
will help achieve best drying performance.
Vent System Chart
Number of
90° turns
Type
or elbows
of vent
0
Rigid metal
1
Rigid metal 16.5 m (54 ft.)
2
Rigid metal 13.4 m (44 ft.)
3
Rigid metal 10.7 m (35 ft.)
4
Rigid metal
Box/
louvered
Angled
hoods
hoods
20 m (64 ft.)
17.7 m (58 ft.)
14.6 m (48 ft.)
11.6 m (38 ft.)
8.8 m (29 ft.)
8.2 m (27 ft.)
6.4 m (21 ft.)