Servicing and Maintenance

11
Inspection and servicing of the installed fire system should occur in accordance with the
relevant Australian Standards (i.e. AS1851 or AS5062). Any alterations to the risk area should
be recorded and where necessary the risk assessment, design calculation and installed
components must be revised to reflect the new operating conditions.
A logbook must be kept, recording all the relevant information from the installation and
servicing. The logbook must contain the following:
Content of logbook:
-
General details
-
Devices used
-
Date and outcome each inspection
-
Risk Assessment
Daily Service Schedule
11.1
A daily inspection should be performed by the operator prior to operation of the equipment. If
anything does not appear normal, the equipment should not be operated and the fire service
provider alerted. The Daily Inspection should include:
-
Visual inspection of the control panel and installed components. These should be accessible
and free from debris, rust, or electrical faults.
-
Visual inspection of the control panel to ensure normal functioning.
normally the only indicator illuminated should be the "Power" indicator (green).
-
Visual inspection of anti-tamper seals and travel pins, to ensure they are in place.
Semi-annual / Annual Service Schedule
11.2
Semi-annual and Annual servicing and maintenance are to be undertaken only by
accredited service technicians. Any misuse of the FIP may result in an accidental discharge
of the suppression system and is not covered by warranty.
Servicing should include a visual inspection of all the installed components to ensure they are in
good condition, and that the relevant stream lengths and thermal clearances are observed as
per the original design calculation and risk assessment.
Operation of the fire system should be tested as outlined in 8. Commissioning.
Fire Detection and Activation System
Appendices of Logbook:
Model 08451
-
Schematic diagrams
-
Photos of the original Installation
-
Programming of the control panel
-
Inspection reports
Rev 3.1
When functioning
Page | 16