FirePro FP-08450 Manual del usuario - Página 10
Navegue en línea o descargue pdf Manual del usuario para Control Panel FirePro FP-08450. FirePro FP-08450 20 páginas. Fire detection and activation system
-
Conventional Detector (Thermal / Smoke): Conventional Detector (P/N FP-08920
Thermal / FP-94140 Smoke) can be connected together in quantities up to 30. A 4k7Ω
End-of-line resistor must be installed in the last detector in the circuit.
-
Detection Not Used: If detection is not used, the supplied end-of-line plugs (marked
green) must be connected to the Circuit 1 Alarm output.
5. Circuit 2 Alarm Circuit:
siren/strobe. Connections for detection and manual call points are the same as Circuit 1
Alarm. If detection is not used, the supplied end-of-line plugs (marked green) must be
connected to the Circuit 2 Alarm output.
6. Discharge Circuit: This circuit should remain disconnected until all other circuits are
connected. The control panel must not be in an alarm/fault condition when the FirePro
generators are connected, as this may cause an accidental discharge. A Universal Test
Lamp (P/N FP-08800) should be connected to take the control panel out of fault condition
and for any commissioning.
-
Mounting FirePro Generators: FirePro Generators must be installed using only
approved brackets with observation of the relevant stream lengths and thermal
clearances noted in the design calculation and risk assessment. Generators should be
mounted near the top of the risk area, with care taken to aim generators away from
openings or obstacles that may impede dispersion of the suppression agent. Egress
routes for personnel must be kept clear, and not be obstructed by any installed
components or by agent dispersion.
This circuit is ALARM ONLY and will only operate the
Page | 10