4.4 FIRE contacts for remote signalling
Volt free changeover contact that will operate whenever the system is triggered
to alarm. This contact is rated for a maximum of 30V DC and 1Amp. These
ratings must not be exceeded.
4.5 FAULT contacts for remote signalling
Volt free changeover contact that will operate when ever there is a fault
condition. This contact is rated for a maximum of 30V DC and 1Amp. These
ratings must not be exceeded
4.6 Connection to addressable modules via FIRE and FAULT contacts
It is possible to configure the FPC-2 such that it will trigger a VMMI1000 addressable
module with fire and fault signals.
To make the FPC-2 compatible with an addressable input module, move jumpers J1 and J2
from their default positions (position A) to position B.
The FIRE NO and C terminals can now be connected directly to the addressable input
module.
Alarm and fault conditions will be indicated on a suitable addressable fire alarm control panel.
Note: The volt free contact function is not available when the contacts are being used to
signal and addressable input module.
Figure 8 - Connection from
FPC-2
to VMMI100 addressable modules
Man-1144 Protection controller Operation manual issue 04