Connection of Multiple FirePro Generators

8
Where multiple FirePro Generators are installed, they must be connected
using the FP-08919 Splitter Lead. The Splitter Lead enables the activation
current to pass to all FirePro generators and for monitoring of the circuit.
Splitter Leads can be installed at any point on the activation circuit and do
not need to be installed adjacent to the fire control panel. For ease of install, servicing and more efficient
field wiring, Splitter Leads should be installed in areas easy to access and minimise extension leads.
Installation
FirePro generators must remain disconnected until system is completed and fire control panel is
8.1
no longer in a fault or alarm condition. The FirePro Universal Test Module (P/N FP-08800) can be
used to take the panel out of a fault condition.
The supply voltage of any system will determine the wiring which can be used
8.2
6vDC Max = 1 FP Units
Where additional units are required in the system a discharge delay module may be required.
8.3
Need to check the system manual for specifications.
Connection of units
8.4
FP Unit 1
FP Unit 1
FP Unit 2
12vDC Max = 2 FP Units
Connection of 2 FirePro Units
Extension Lead
Connection of 4 FirePro Units
FP Unit 3
Local Application Fire System
FP Unit 2
Extension Lead
FP Unit 4
FP-08917
24vDC Max = 4 FP Units
Activation
Splitter
Lead
Splitter Lead
Activation
Cable
Rev 3.1
Cable
Page | 7