FirePro Sigma XT Manual de instalación y funcionamiento - Página 6

Navegue en línea o descargue pdf Manual de instalación y funcionamiento para Alarmas contra incendios FirePro Sigma XT. FirePro Sigma XT 14 páginas. Conventional fire control panel with control unit for aerosol release, system isolation
También para FirePro Sigma XT: Procedimiento (4 páginas)

3.1.2.

Connecting more than 3 Signs

For systems requiring more than 3 signs (or devices), wiring is as follows:
Notes: •
FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS.
Connections for the first 3 signs or devices remains the same as the previous wiring diagram.
For more than 3 signs, a separate power supply is required from the 24VDC output on the FIP.
STATUS SERIAL (RS485) - Maximum number of devices, including both Signs and LCS, for the 485
communications is 7. RS485 connection remains the same for all 7 devices.
Sigma_XT_signs_m3.5.docx
Page 6 of 14