Montering vid risk för kondensproblem,
t.ex. kallvind eller utomhus.
Extern LED som
larmindikering.
Remote LED
indication.
Håltagning Ø 38 mm.
Drill a hole Ø 38 mm.
Monteringsbeslag för rund eller
isolerad plan kanal.
Med hjälp av monteringsbeslaget kan kanal-
diametern vara så liten som 100 mm.
Monteringsbeslaget levereras plant.
The mounting bracket is supplied flat.
Monteringsbeslaget är lätt att böja/forma så
att det passar runda eller plana kanaler.
The mounting bracket can easily be bent or
shaped to fit circular or rectangular duct.
SLUTKONTROLL
• Kontrollera att riktningspilarna pekar i flödesriktningen.
• Kontrollera att pluggen till testhålet sitter i ordentligt.
• Kontrollera att flödesindikatorn visar på flöde (vippar).
• Fullskaleprov med rökgenerator rekommenderas för
kontroll av rökdetektorns funktion.
Felsökning.
Rökdetektorn larmar utan rökpåverkan.
• Rökdetektorn är trasig, smutsig eller placerad så att kondens bildas.
Se punkt 9. Detektorinsatsen behöver bytas ut.
Endast kontrollenheten larmar.
• Kontrollera att slutmotståndet är monterat i sista rökdetektorn.
• Kontrollera att slingans motstånd är 2,2kΩ från kontrollenheten.
• Kontrollera att kontrollenheten är OK genom att montera 2,2kΩ
motståndet i rökdetektorutgången på kontrollenheten.
• Kontrollera med hjälp av en voltmeter att 21-24 VDC med rätt
polaritet finns i plint 1 (-) och plint 2 (+) på Uniguard.
!
Enligt WEEE (Waste of Electrical and Electronic Equipment)
direktiv, skall produkten när den är förbrukad lämnas separat hos
ett härför avsett insamlingsställe och inte placeras bland osorterat
avfall. Alternativt returnera den till Calectro för återvinning.
DOLD rökdetektor
HIDDEN smoke detector
Skylt
Sign
Isolermatta 100-200 mm används för att
täcka hela Uniguarden vid montering
på kallvind. Anvisningsskylt bör monteras.
Use insulation cover of 100-200 mm and
protect the entire Uniguard. A sign should
be used to show location of the detector.
Håltagning
Ø 51 mm.
Drill a hole
Ø 51 mm.
Mounting in places where possible
9
condensation problems could arise,
e.g. cold attics or outdoor.
Håltagning Ø 38 mm.
Drill a hole Ø 38 mm.
Mounting bracket for circular or
10
insulated rectangular ducts.
Using the mounting bracket
the diameter of the duct can
be as small as 100 mm.
Fäst beslagets
ben på kanalen.
Fix the bracket
on to the duct.
Gummi-
tätning.
Rubber
gasket.
Rund kanal.
Circular duct.
• Check that the air flow direction arrows have the same direction
as the air flow in the duct.
• Check that the plastic plug of the test hole is properly mounted.
• Check that the flow indicator oscillates ensuring proper air flow
through the detector.
• It is recommended that smoke from a smoke generator is
introduced into the duct to check the detector's function.
Trouble shooting.
The smoke detector indicates alarm without smoke.
• Smoke detector is faulty, contaminated with dirt or condensation. See
para 9. The detector needs to be replaced.
Only the control unit indicates alarm.
• Check that the end resistor is mounted in the last smoke detector.
• Check that the resistance in the smoke detector loop is 2,2kΩ.
• Check that the control unit is OK by placing the 2,2kΩ resistor directly
on the smoke detector output of the control unit.
• Check with a voltmeter, that 21-24 VDC is present in terminal 1 (-)
and terminal 2 (+) on the Uniguard. Note! The voltage must have the
correct polarity.
According to WEEE (Waste of Electrical and Electronic Equipment)
directive, you must at the end of life of the product dispose of it
separately at an appropriate collection point and not place it with
unsorted waste. Alternatively return it to Calectro for recycling.
Vid montering i kanal utomhus används
isolerande skyddshuv/låda UG-COVER.
For outdoor location use protection
cover e.g. Calectro´s UG-COVER.
Gummi-
tätning.
Rubber
gasket.
Isolerad, plan kanal.
Insulated rectangular duct.
FINAL CHECKS
!