MENU SYSTEM
Three push buttons are used to change settings
on and program the CALAIR-PR-230V. The but-
tons can also be operated when the cover has
been removed. The top ▲ and bottom ▼ buttons
are used to scroll through the menu system and
change settings (such as setpoints). The middle
button
is used to confirm and execute.
Row
Main menu
Sub menu 1
[Main menu]
1
Regulator menu
Setpoint
2
3
Calibrate sensor
4
5
Output range
6
7
Regulator speed
8
9
Mean value op.
mode
10
11
12
Back
13
Temperature
Temp. sensor
menu
14
15
16
17
Temp. comp. range
18
19
20
Temp. comp.
21
22
Temp. adj.
23
Back
24
Alarm menu
Alarm log
25
High press. alarm
26
27
28
29
Low press. alarm
30
31
32
33
Alarm delay
34
35
Back
36
Misc. menu
Output override
37
6
Press the middle button to access the menu system.
Time-out function: The display returns to normal
mode if no button is pressed within 90 seconds.
Changed settings (such as setpoints) must be con-
firmed by pressing the middle button, within 20 sec-
onds. The setting will otherwise not be saved and the
display will return to the previous sub menu and, after
a further 90 seconds, to the normal display mode.
Sub menu 2
Display text / factory
setting
Set setpoint
150Pa
(0-2000Pa)
Calibrate sensor
Please wait...
Done! Press enter
to exit
Set output min/max
Min: 0%
Max: 100%
Set regulator speed
3
(1-10)
Set mean op. mode
Actual value
1.3 sec.mean value
2.6 sec.mean value
Set temp. sensor type
Pt1000
CALAIR-PR-NTC
NONE/OFF
MB EXT
Set temp. comp. range
Low: -15°C
High: +15°C
(-20 - +30°C)
Set temp. comp.
50Pa
(Decreases the set-
point by (0-500Pa))
Set temp. adj.
0.0°C
Alarm log
No items found >Back
Set high press. alarm
Disabled
Enabled
2000Pa
(0-2000Pa)
Set low press. alarm
Disabled
Enabled
0Pa
(-50-2000Pa)
Set pr. alarm delay
3 min
(0-10 minutes)
Output override
Disabled
Enabled 0.0V (0.0-
10.0V)
Information
Current setpoint.
Settings range.
Zero pressure calibration is being carried out.
Zero pressure calibration ready.
Min. 0-10V output signal.
Max. 0-10V output signal.
Adjustable control rate: 1=slow, 10=quick (3=previ-
ous model CALAIR-PR).
Settings range.
No average pressure measurements available.
1.3 second pressure measurement average.
2.6 second pressure measurement average.
Back to main menu.
Selection of Pt1000 temperature sensor.
Selection of NTC temperature sensor (as previous
model CALAIR-PR).
No temperature sensor connected.
Selection that temperature is obtained via Modbus.
Temperature at maximum setpoint adjustment.
Temperature when setpoint adjustment starts.
Settings range
The number of Pascal which the setpoint is lowered
[Low:]: refer to row 17 above.
Explanation and settings range.
Adjustment of temperature measurement. -3.0°C to
+3.0°C.
Back to main menu.
Alarm log.
The high pressure alarm function is shut off.
The high pressure alarm function is activated.
Current limit value for high pressure alarm.
Settings range.
The low pressure alarm function is shut off.
The low pressure alarm function is activated.
Current limit value for low pressure alarm.
Settings range.
Current alarm delay.
Settings range.
Back to main menu.
Temporary manual override of output signal i.e.
when adjusting. Automatically reset after 10
hours.
Settings range.