aldes MR Modulo Manual - Página 8
Navegue en línea o descargue pdf Manual para Controlador aldes MR Modulo. aldes MR Modulo 16 páginas. Constant airflow regulator mr
Constant Airflow Regulator MR
MR Mono - MR Modulo
INSTALLATION
• The MR will push-fit into circular ducts in close proximity to a take-off or a terminal.
• It is important to observe the MR orientation corresponding to the airflow direction indicated on the MR.
• Horizontal / vertical mounting possible.
• In order to avoid acoustic and aeraulic disturbance it is recommended to respect the following distance between the MR and the terminal
(grille / diffuser / inlet):
- in exhaust: D = 1 Ø,
- in supply: D = 3 Ø.
Air exhaust
MR Modulo mounting and setting
1. Adujst the airflow setting
Rotate the adjustment ring for a tool-free airflow setting until the desired airflow according to the correlation table.
2. Position the MR Modulo
Introduce the MR in the duct according to the arrow which shows
the airflow direction. Minimum straight upstream and downstream
distances must be observed. There is no recommendation regarding
the membane positioning.
8
Small diameters
Air supply
360°
3. Product localization
MR Modulo is delivered with a sticker which will be needed to be
manually filled on site (MR diameter and airflow setting) and placed
directly onto the duct to show where the MR Modulo has been
mounted.
Big diameters