aerauliqa QR590E Manual de instalación - Página 12
Navegue en línea o descargue pdf Manual de instalación para Sistema de calefacción aerauliqa QR590E. aerauliqa QR590E 20 páginas. Energy recovery ventilation unit with enthalpic heat exchanger
Installer menu
1 Language
2 Date/Time
3 Machine orientation
4 Bypass settings
5 Heating
Installer menu
1 Language
2 Date/Time
3 Machine orientation
4 Bypass settings
5 Heating
Installer menu
1 Language
2 Date/Time
3 Machine orientation
4 Bypass settings
5 Heating
Installer menu
6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter
Installer menu
6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter
12
It allows to select the orientation of the duct connections from and to outside (LEFT or
RIGHT - paragraph 3.3).
Press OK to enter.
Use or to choose.
Press OK for setting.
The factory setting (DEFAULT) is LEFT.
It allows to set the Bypass operation parameters
Press OK to enter.
Use or to choose "Desired Temperature", "Tmax Free Heating", "Tmin Free Cooling"
For definitions see "Bypass" (paragraph 7.3)
Press OK to select.
The setting ranges are:
Desired Temperature: 15°C ÷ 30°C
Tmax Free Heating: 25°C ÷ 30°C
Tmin Free Cooling: 15°C ÷ 20°C
Use or to increase or decrease the temperature.
Press OK to select.
Press ESC to go back to the previous menu.
The factory settings (DEFAULT) are:
Desired Temperature: 23°C
Tmax Free Heating: 28°C
Tmin Free Cooling: 18°C
To be selected only in case an external heating element (not supplied) is present.
Press OK to enter.
Use or to choose NO/PRE/POST.
Press OK to select.
The factory setting (DEFAULT) is NO.
NO: HEAT output (Fig. 5.g) is never activated
PRE: the heating element is intalled at "intake air side" (Fig. 7.a - ).
HEAT output (Fig. 5.g) is activated and heating icon displays on LCD when
T21 < HEATING THRESHOLD (Fig. 7.a)
POST: the heating element is intalled at "supply air side" (Fig. 7.a - ).
HEAT output (Fig. 5.g) is activated and heating icon displays on LCD when
T11 < HEATING THRESHOLD (Fig. 7.a)
This option displays only if "Heating" is set on PRE or POST.
It allows to set the heating threshold in case of PRE or POST heating.
Press OK to enter.
Use or to set the temperature.
Press OK to select.
Setting ranges:
PRE: -20°C ÷ 0°C
POST: +15°C ÷ +25°C
The factory settings (DEFAULT) are:
PRE:-10°C
POST:+20°C
To be selected only in case an external dehumidifier (not supplied) is present.
Press OK to enter.
Use or to choose NO or YES.
The factory setting (DEFAULT) is NO.
The DH relay output is activated when the HY input is activated (Fig. 5.g) and the icon
is displayed.
Note: in case dehumidifier is installed, the BST input (Fig. 5.g) is used as alarm output.
A
C