Aldrich A3C-4000 Datos del producto

Navegue en línea o descargue pdf Datos del producto para Caldera Aldrich A3C-4000. Aldrich A3C-4000 5 páginas. Firetube condensing hydronic boilers

A3C Series Condensing Hydronic Boilers
Models: A3C-1000, A3C-1500, A3C-2000, A3C-2500
A3C-3000, A3C-4000, A3C-5000, A3C-6000
ALDRICH SERIES A3C FIRETUBE CONDENSING HYDRONIC BOILERS
PART 1 – GENERAL
1.1
SUMMARY
A. This section includes packaged, factory-fabricated and assembled, gas-fired, three pass
condensing firetube boilers, trim, and accessories for generating hot water for pressure as
noted on plans.
1. Three pass firetube condensing boiler
2. Burner - Specify Fuel: Natural Gas, LP Gas or Combination Gas/#2 Oil
1.2
SUBMITTALS
A. Product Data: Include performance data, operating characteristics, furnished specialties,
and accessories.
B. Shop Drawings: For boilers, boiler trim, and accessories; Include plans, elevations, sections,
details, and attachments to other work.
1. Wiring Diagrams: Power, signal, and control wiring.
2. Fuel Train Schematic
1.3
CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For boilers, components, and accessories to include in
emergency, operation and maintenance manuals.
B. Warranties: As specified in this section.
1.4
QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction.
B. ASME Compliance: Fabricate and label boilers to comply with ASME Section IV Boiler and
Pressure Vessel Code.
C. ASHRAE/IESA 90.1 Compliance: Boilers shall have minimum efficiency according to: Gas and
Oil Fired Boilers – Minimum Efficiency Requirements."
D. UL Compliance: Control devises and control sequences according to requirements of UL.
E. CSD-1 Compliance: Boilers/burners equipped to meet current state code.