AM Series Thermal Insulation Replacement Instruction
4. Removing the Burner
Complete the following instructions on each burner in the unit.
1.
Prepare a suitable cover for the burner so that no dirt, water, or other foreign objects fall
into the burner unit from above.
2.
Referring to in Figure 1, loosen screws labeled "D" and then move the ignition
transformer, labeled "A," up.
3.
Referring to in Figure 2, disconnect the two wires labeled "D" from the ignition electrodes,
disconnect the wire labeled "E" from the flame detection electrode (flame rod), and rotate
the air inlet silencer labeled "B" in the up direction.
4.
Pull the air inlet silencer to the left (label "C") and remove it from the fan.
07/28/2014
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Kit # 62632006
Removing the Burner
Figure 1: Removing the Spark Generator
Figure 2: Removing the Air Inlet Silencer
TID-0120_0A
Page 3 of 10