Armstrong 4302 Series Manual - Página 7

Navegue en línea o descargue pdf Manual para Bomba de agua Armstrong 4302 Series. Armstrong 4302 Series 8 páginas. Dualarm vertical in-line pumps

Typical Specifications

Series 4302 Split Coupled
Vertical In-Line Pump
Supply and install as shown on the plans and specifications,
Armstrong Series 4302 dualARM split coupled Vertical In-Line
centrifugal pumping unit. The cast casing with equal size suction
and discharge flanges, having separate tapped flush line and
pressure gauge connections, shall incorporate two radially split,
single stage centrifugal pumps. Each pump shall have a cast bronze
dynamically balanced impeller, stainless steel shaft, lower seal flush
throttle bushing, outside balanced mechanical seal with stainless
steel parts, Viton secondary seal, carbon vs silicone carbide faces
and stainless steel gland plate and hardware. Each pump shall be
fitted with a factory furnished flush line to the mechanical seal. The
flush line is to be fitted with a manual air vent.
Each driving motor shall be an industry standard vertical solid
shaft, squirrel cage induction type, built to nema standards(motor
efficiency levels may be specified). The motor shall have
enclosure and be suitable for a
Volt power supply and shall be connected to the pump by means
of a rigid split type spacer coupling that permits removal of the
mechanical seal without disturbing the pump or motor connections.
The inlet and outlet ports on the casing shall be at least one size
larger than the single pump size, so that both units may operate
in parallel with no loss of single pump efficiency. Each port shall
be fitted with an isolation valve that allows the units to operate in
parallel or standby. It may also be used to isolate one pumping unit
for servicing or removal, while the other pump remains operating.
Flush line option:
Supply in the flush line to the mechanical seal a 50 micron cartridge
type filter (if the differential pressure exceeds 30 psig [2 bars], a
Cyclone separator may be specified) and a sight flow indicator. The
mechanical contractor shall change the filter cartridge after the
system has been flushed and on a regular basis thereafter, until the
building is turned over to the owner.
Hz,
Phase,
Series 4382 Close Coupled
Vertical In-Line Pump
Supply and install as shown on the plans and specifications,
Armstrong Series 4382 dualARM close coupled type Vertical In
-Line centrifugal pumping unit. The cast casing with equal size
suction and discharge flanges, having separate tapped flush line
and pressure gauge connections, shall incorporate two radially
split, single stage centrifugal pumps. Each pump shall have a
cast bronze dynamically balanced impeller, bronze shaft sleeve
and inside type single spring mechanical seal with carbon* vs
silicone carbide faces. Each pump shall be complete with a factory
furnished flush and vent line.
Each driving motor shall be an industry standard vertical solid
shaft, squirrel cage induction type, built to nema standards(motor
efficiency levels may be specified). The motor shall have
enclosure and be suitable for a
Volt power supply. The inlet and outlet ports on
the casing shall be at least one size larger than the single pump
size, so that both units may operate in parallel with no loss of
single pump efficiency. Each port shall be fitted with an isolation
valve that allows the units to operate in parallel or standby. It may
also be used to isolate one pumping unit for servicing or removal,
while the other pump remains operating.
* For liquids above 200°f / 93°c use: antimony loaded carbon
For Glycols greater than 30% by wt use: silicon carbide
Hz,
Phase,