Armstrong The Brain DRV80 Manual de solución de problemas - Página 3
Navegue en línea o descargue pdf Manual de solución de problemas para Unidad de control Armstrong The Brain DRV80. Armstrong The Brain DRV80 5 páginas. Modbus networking
También para Armstrong The Brain DRV80: Manual de instalación y funcionamiento (16 páginas)
Armstrong Hot Water, Inc. – DRV40-80 Gen. 2 Troubleshoot Guide
221 Armstrong Blvd., Three Rivers, Michigan 49093 – U.S.A. Phone: (269) 279-3602
Battery Error
Check
Has the valve been reset
No
(i.e. powered off, then on)?
Yes
Have the batteries been
No
replaced within last year?
Yes
Are all cables/wires &
No
connectors ok?
Yes
Is the valve PCB
No
operational and ok?
Yes
Is the valve PSU
No
operational and ok?
Yes
Issue addressed or Contact
Factory @ 269-279-3602
Reset the valve by
powering down & then
powering back on
Replace Batteries
Ensure all wires are not
pinched & plugs are
connected
Replace Ele. Housing
Replace Ele. Housing
Intelligent System Solutions®
armstronginternational.com
Fax: (269) 279-3130
Display Issues
Check
Has the valve been reset
(i.e. powered off, then on)?
Yes
Is the lighting/brightness
sufficient?
Yes
Is the display
numerals/characters ok?
Yes
Issue addressed or Contact
Factory @ 269-279-3602
PSU = Power Supply
PCB = Printed Circuit Board
S T E A M ● A I R ● H O T W A T E R
Reset the valve by
No
powering down & then
powering back on
Adjust brightness via
No
POT adjustment screw on
PCB
Replace display & keep
original to allow for a
No
spare in event heat
affects again
Key:
GDA = Gear Drive Assembly