7.2 Duct Kit Installation

1. Select a point along the duct where the probe assembly can be installed into unrestricted
airflow without interfering with any internal duct components such as dampers, radiators,
etc.
2. Mark and drill the four holes for the duct probe as shown in Figure 4. The centerline
must be parallel to the air flow through the duct.
3. Install the duct probe assembly through the holes just drilled. The sample port must be
on the upstream side. Secure the probe assembly in place with the two sheet metal
screws.
4. Connect the open ends of the two tubes from the probe assembly to the two sample
ports on the base of the Model 310. It makes no difference which tube is connected to
which port on the Model 310.
Figure 4: Duct Probe Installation Dimensions
AMC-310 AirSense Infrared CO
Analyzer
2