5 OPERATION AND CALIBRATION
5.1 OPERATION
Note:
BEFORE turning on the main power to the monitor, MAKE SURE all connections are
properly made.
Once power has been turned on, the GREEN power LED will light. A one-minute time delay
eliminates false alarms from occurring during the sensor's warm up period. After this time
delay, the unit becomes fully operational.
indicator is not needed, the three-circuit miniature switch can be set accordingly. Refer to
Section 3, Item 9 and Figure 1.
If any gas surrounding the sensor exceeds the low alarm trip point setting, the YELLOW LED
and low alarm relay will be activated. If any gas exceeds the high alarm trip point setting, the
RED LED, high alarm relay and audio alarm will be activated. An open sensor/transmitter circuit
is indicated by the amber fail LED.
5.2 CALIBRATION
The AMC-1044-T series monitor is factory calibrated at levels based on set standards.
As the calibration procedure may cause the monitoring equipment to give a false alarm,
appropriate precautions should be taken. Instructions on introducing the gas sample are
included with the sensor/transmitter manual. Refer to the transmitter manual for calibration and
required equipment.
NOTE
BEFORE MAKING ANY CHANGES TO ALARM LEVEL SETTINGS WE RECOMMEND
CONSULTING THE ARMSTRONG MONITORING CORPORATION FOR ADVICE ON SETTING THE
PROPER TRIP POINT VOLTAGE FOR A SPECIFIC ALARM CHANGE.
5.2.1 CALIBRATION FOR REMOTE SENSOR/TRANSMITTER
Please refer to applicable Sensor/Transmitter manual for calibration instructions.
5.2.2 ALARM ADJUSTMENTS FOR TRANSMITTER
Alarms are set at the factory and do not need to be adjusted unless a change in alarms is
required.
Low alarm adjust is used to establish the low alarm trip point. This is done by adjusting the
voltage to the appropriate fraction of full scale at test points COM and LOW TP (see Figure 7).
AMC-1044-T Monitor
If time delays are required or the audio alarm