HVAC Installation
HVAC PRE-INSTALLATION CHECKLIST
1.
Confirm the area to be scented.
2.
Locate the Air Handling Unit or duct that serves the area to
be scented.
3.
Make sure the Air Handling Unit does not use an open gas
flame.
4.
Locate and mark the optimal position for the Scent Point.
5.
Locate and mark the exact location for placement of the scent
diffuser.(See Figure A page 13)
6.
Confirm the distance between the Scent Point and the proposed
scent diffuser location. (Air tube should be max 3 feet.
Avoid dips and coils or lows in the air tube. The Scent Point
should ALWAYS be higher than the scent diffuser).
7.
Locate and install 110 or 220V AC power outlet close to the
diffuser install location.
Avoid placing the power outlet directly under the scent
diffuser.
14
SCENT DIFFUSER POSITIONING
It is important to locate an insertion point where the scent
output will be smoothly drawn into and mixed with the airflow.
This usually means those parts of the AHU where the static
pressure is negative.
IDEAL LOCATIONS
—
Before the supply fan with injection through the wall of the
AHU. Positioning immediately before the fan and after the
coils if possible or in the mixed air chamber.
—
Behind the blower with the entire scent diffuser mounted
inside the AHU in the mixed air chamber.
—
Outside the AHU in the Supply Air duct.
—
Best practice when installing in an AHU is to place the hose
guide after the heating and cooling coils. If this is not
possible, the scent output can pass over hot water, steam,
chilled water, and DX coils.
OPEN GAS FLAMES SHOULD ABSOLUTELY BE AVOIDED. IF INSTALLATION
MUST BE OVER GAS HEATED COILS OR OPEN GAS FLAMES, CONTACT
AROMATECH TECHNICAL SUPPORT