TROUBLESHOOTING
7
Troubleshooting
If problems arise with the water separator VT2 please check the following points. Should
the fault not be located please contact your technical advisor.
Danger of injury by electric shock and risk of material damage
The device may only be repaired by trained specialised staff.
WARNING
Any work carried out by unauthorised persons shall lead to
Faults
Problem
Compressor
(soundbox
VP2/VP3/VP6) does
not start running or
has automatically
switched off
Compressor
(soundbox
VP2/VP3/VP6) draws
in water
"Pump Fault"
appears
in the display
Page 12 of 15
Within the warranty period, any work on the device shall only
be carried out by the manufacturer or persons commissioned
by him.
the forfeiture of all warranty claims!
Possible cause
Power plug not
plugged into VT2
socket outlet
Socket outlet fuse has
tripped
Circuit breaker (of
connected soundbox)
tripped
Connected soundbox
defective
Compressor is not
connected to the
appliance socket of the
VT2, but to permanent
voltage
Waste water hose
too long or too thin
Pump soiled
Remedy
Plug in power plug
Check the
drying construction! Maximum
current consumption at
appliance socket: 16 A!
Let the soundbox cool down and
check the installation.
Arrange for repair by expert staff
Connect compressor to VT2
appliance socket
Shorten waste water hose
Clean pump