Environmental conditions
Operating temperature: – 10 to + 55 °C
Storage temperature:
– 40 to + 70 °C
Relative humidity of
annual mean:
≤ 75%
Altitude:
2000 m max.
Indoor use statement!
4. Mounting
The SINEAX U554 can be mounted on a top-hat rail.
Note "Enironmental conditions" in Section
"3. Technical data" when determining the place
of installation!
Simply clip the device onto the top-hat rail (EN 50022) (see
Fig. 1).
Fig. 1. Mounting onto top-hat rail 35 × 15 or 35 × 7.5 mm.

5. Electrical connections

Connect the electrical conductors acc. to the instructions
on type label.
Make sure that all input cables are not live
(potential-free) when making the connections!
Impending danger by high input voltage or
high power supply voltage!
Also note that, ...
... the data required to carry out the prescribed
measurement must correspond to those mar-
ked on the nameplate of the SINEAX U554
(
measuring input,
and
power supply, see Fig. 5)!
... the resistance in the output circuit may not
overrange the current output value
R
max. [kΩ] ≤
ext
(I
= current output value)
AN
and not underrange the voltage output value
R
min. [kΩ] ≥
ext
(U
= voltage output value)
AN
... the measurement output cables should be
twisted pairs and run as far as possible away
from heavy current cables!
In all other respects, observe all local regulations
when selecting the type of electrical cable and
installing them!
measuring output
15 V
I
[mA]
AN
U
[V]
AN
4 mA
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
U
Fig. 2. Power supply to
terminals 8 and 9.
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
U
Fig. 4. Power supply internal from measuring
input, power supply not required.
Conformity
Meas. output
Output signal
marks
+
3,7
0 - 4-20mA
SINEAX U554
Ord: 123/456789/996/101
0-60-100V 50/60Hz
U
Meas. input
Meas. range
Meas. quantity
Fig. 5. Declaration to type label.

6. Commissioning and maintenance

Switch on the power supply and the measuring input. It is
possible during the operation to disconnect the output line and
to connect a check instrument, e.g for a functional test.
No maintenance is required.
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
U
Fig. 3. Power supply connected
to the low tension to terminals
12 and 13.
U
= Measuring input
= Measuring output
= Power supply
0,5
Camille Bauer AG
Switzerland
Works.
No.
85-230V AC/DC
40-400Hz 3VA
+
Power supply
7