13.4 XR80D: 20A COMPRESSOR
3
4
20(8)A/250Vac
15 16 17 18 19
Comp
Line
24Vac/dc supply: connect to the terminals 11 and 12.
120Vac supply: connect to the terminals 11 and 12.
230Vac supply: connect to the terminals 11 and 12.
1592007271 XR80C-D GB r1.0 20.05.2005.doc
Installing and Operating Instructions
Power
Supply
230Vac
11 12
8(3)A/250Vac
n.c.
14. DEFAULT SETTING VALUES
Label
Set
Set point
Hy
Differential
LS
Minimum set point
US
Maximum set point
Ot
Thermostat probe calibration
OdS Outputs delay at start up
AC
Anti-short cycle delay
COn Compressor ON time with faulty probe
COF Compressor OFF time with faulty probe
CF
Temperature measurement unit
rES Resolution
AgC Agitator configuration
tIC
Resolution for the Agt parameter
IAg
Interval between agitation cycle
Agt Length for agitation cycle
APO First agitation cycle after start up
ALc Temperat. alarms configuration
ALU MAXIMUM temperature alarm
ALL Minimum temperature alarm
ALd Temperature alarm delay
dAo Delay of temperature alarm at start up
PbC Probe selection
rEL Software release
Ptb
Map code
Hidden parameters
Dixell S.p.A. Z.I. Via dell'Industria, 27
32010 Pieve d'Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail: [email protected] - http://www.dixell.com
XR80C – XR80D
R1.0 1592007271
Name
Range
LS÷US
0,1÷25.5°C/ 1÷ 255°F
-50°C÷SET/-58°F÷SET
SET÷150°C/ SET ÷ 302°F
-12÷ 12°C / -120 ÷ 120°F
0÷255 min
0 ÷ 50 min
0 ÷ 255 min
0 ÷ 255 min
°C ÷ °F
in ÷ dE
EL=with compressor;
in=independent
nP=minutes; Pb=seconds
1÷120min
0÷255min
y=immediately; n=after IAG
rE; Ab
ALL÷150.0°C; ALL ÷302°F
-50.0°C÷ALU/ -58°F ÷ ALU
0 ÷ 255 min
0 ÷ 23h e 50'
Ptc ÷ ntc
Values
2.0
2.0
-30.0
20.0
0.0
0
1
15
30
°C
dE
EL
nP
15
3
n
Ab
100
-50.0
15
1.3
ntc/Ptc
--
1.2
--
--
4/4