5.4 Control mode
Display
ΔP Measurement
200 Pa
menu
unit metric
operating mode
control mode
parameter
diff. pressure
setpoint 1
50 Pa
setpoint 2
250 Pa
output voltage
U = 10,0 V DC
P - parameter
50
l - parameter
3,15
controlling mode
positive / heating
back and confirm
Start menu: Press button T1 approx. two seconds
Press button T2 to get to the next menu item
Press button T1 to switch between:
metric <=> imperial
Press button T2 to get to the next menu item
Press button T1 to switch between:
measuring mode <=> control mode
Press button T2 to get to the next menu item
Press button T1 to switch between:
diff. pressure <=> volume flow
Press button T2 to get to the next menu item
If selected parameter = diff. pressure
resp. after the input of the k-factor follows:
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
Press button T1 to switch between:
positive / heating <=> negative / cooling
Press button T2 to go to the next menu
Press button T1 to leave the menu
Press button T2 to stay in the menu
Doc.-no.: DPC200_01_EN
Action
Issue: 11/2015
OPERATION