Altronix ACM220 Series Manual de instalación - Página 2
Navegue en línea o descargue pdf Manual de instalación para Controlador Altronix ACM220 Series. Altronix ACM220 Series 13 páginas. Access power controllers with power supplies
![Altronix ACM220 Series Manual de instalación](/uploads/products/server2/858586/858586.jpg)
Altronix ACM220 Series units distribute and switch power to access control systems and accessories. They convert
a nominal 220VAC (working range 198VAC - 256VAC), 50/60Hz input into eight (8) independently controlled 12VDC
or 24VDC fuse protected outputs. These power outputs can be converted to dry form "C" contacts. Outputs are acti-
vated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader,
Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag
Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes.
The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices.
The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
ACM220 Series Configuration Reference Chart:
Altronix
Model Number
AL400ACM220
AL600ACM220
AL1012ACM220
AL1024ACM220
Input:
• Power supply input options:
a) One (1) common power input for ACM8 and
lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8 and one (1) for lock accessory power
(external power supply is required). Current is
determined by the power supply connected,
not to exceed a maximum of 10A total.
• Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
Output:
• 12VDC or 24VDC outputs.
• Eight (8) independently controlled outputs.
Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure
power outputs.
b) Eight (8) form "C" 5A rated relay outputs
c) Any combination of the above.
• Eight (8) auxiliary power outputs (unswitched)
• Output fuses are rated @ 3.5A.
• Filtered and electronically regulated outputs
(built-in power supply).
Visual Indicators:
• Red LEDs indicate outputs are triggered
(relays energized).
• Green LED indicates FACP disconnect is triggered.
• AC input and DC output LED indicators.
- 2 -
12VDC
24VDC
Total
Total
Output
Output
Current
Current
4A
3A
6A
6A
10A
–
–
10A
Specifications:
Overview:
Individual
Fused
Output
Outputs
Rating
8
3.5A
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• AL400XB2V, AL600XB220, and AL1012XB220
(Power Supply Board) maximum charge current 0.7A.
AL1024XB2V (Power Supply Board) maximum
charge current 3.6A.
• Automatic switch over to stand-by battery when
AC fails.
• AC input and DC output LED indicators.
• Zero voltage drop when unit switches over to
battery backup (AC failure condition).
• Battery fail and battery presence supervision
(form "C" contact).
Features:
• Fire Alarm disconnect (latching or non-latching) is
individually selectable for any or all of the
eight (8) outputs.
• Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• Alarm output relay indicates that FACP input is
triggered (form "C" contact rated @ 1A 28VDC).
• Short circuit and thermal overload protection.
Enclosure Dimensions (H x W x D approx.):
• 15.5" x 12" x 4.5"
(393.7mm x 304.8mm x 114.3mm)
• Enclosure accommodates up to
two (2) 12AH batteries.
220VAC
Power
50/60Hz
Supply
Input
Board
Current
Input
Draw
Fuse Rating
1.2A
1.5A
5A/250V
2.2A
3A
ACM220 Series Installation Guide
Power
Supply
Board
Battery
Fuse Rating
15A/32V
–
15A/32V