6. Connect FACP output to desired AL800LGK logic board inputs, and notification appliances to desired AL800LGK
logic board outputs (see Application Guide).
Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with
synchronization capability.
7. For connection of smoke detectors, digital dialer see Optional Hookup Diagram, pg. 8.
Class A, Style Z Class B, Style W, Y, SW1 & SW2 Settings:
• For all Class B, Style W, Y, hookups SW1 & SW2 on the AL800LGK logic board must be open.
For all Class A, Style Z hookups SW1 & SW2 on the AL800LGK logic board must be closed.
Outputs must be programmed independently (OUT1 - OUT4)
Function
Input to Output
Follower Mode
Temporal
Code 3 Mode
Steady Mode
For the above modes Dip Switch 4 determines which Input controls
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Switch Positions
Function
ON
1, 3,
Amseco Sync
Mode*
Faraday
2, 4
Sync Mode*
Gentex
®
1, 2,
Sync Mode*
3, 4
Gentex is a registered trademark
of Gentex Corporation.
System Sensor
®
Sync Mode*
1, 2, 4
System Sensor is a registered
trademark of Honeywell.
CooperWheelock
®
Sync Mode*
2, 3, 4
CooperWheelock is a
registered trademark of
Cooper Wheelock.
*Note: The AL1002ULADA will only synchronize horns, horn/strobes and strobes that contain synchronization capability.
Contact signal manufacturer for more detailed info. The same synchronization mode must be selected for all outputs.
Note: It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification
appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while
visual notification appliances (strobes) continue to operate.
- 4 -
Output Programming Selection Table:
Switch Positions
Descriptions
ON
OFF
Output follows signal it receives from the corresponding input (i.e. FACP
1
2, 3
Sync module - maintains synchronization of notification appliance circuit).
Enables Temporal Code 3 signal generation output.
3
1, 2
This mode will accept a steady or a pulsing input.
A steady output signal will be generated.
1, 2, 3
This mode will accept steady or pulsing input.
Sync Mode Selection Table:
Descriptions
OFF
This mode is designed to work with the Amseco series of horns, strobes, and horn/
strobes to provide a means of synchronizing the Temporal-coded horns, synchro-
2
nizing the flash timing of the strobe, and silencing the horns of the horn/strobe
4
combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Faraday series of horns, strobes, and horn/
strobes to provide a means of synchronizing the Temporal-coded horns, synchroniz-
1, 3
ing the flash timing of the strobe, and silencing the horns of the horn/strobe combina-
tion over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Gentex
strobes to provide a means of synchronizing the Temporal-coded horns, synchroniz-
ing the flash timing of the strobe, and silencing the horns of the horn/strobe combina-
tion over a two-wire circuit while leaving strobes active.
This mode is designed to work with the System Sensor
horn/strobes to provide a means of synchronizing the Temporal-coded horns, syn-
3
chronizing the one-second flash timing of the strobe, and silencing the horns of the
horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the CooperWheelock series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-coded horns,
1
synchronizing the one-second flash timing of the strobe, and silencing the horns of
the horn/strobe combination over a two-wire circuit while leaving strobes active.
(AL800LGK Board)
Output Dip Switches
series of horns, strobes, and horn/
®
series of horns, strobes, and
®
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC