Altronix AL1002ULADA Manual de instalación - Página 4
Navegue en línea o descargue pdf Manual de instalación para Extensor Altronix AL1002ULADA. Altronix AL1002ULADA 13 páginas. Nac power extenders
También para Altronix AL1002ULADA: Manual de instalación (17 páginas), Manual de aplicación (8 páginas), Manual de aplicación (8 páginas), Manual de aplicación (8 páginas)

6. Connect FACP output to desired AL800LGK logic board inputs, and notification appliances to desired AL800LGK
logic board outputs (see Application Guide).
Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with
synchronization capability.
7. For connection of smoke detectors, digital dialer see Optional Hookup Diagram, pg. 8.
Class A, Style Z Class B, Style W, Y, SW1 & SW2 Settings:
• For all Class B, Style W, Y, hookups SW1 & SW2 on the AL800LGK logic board must be open.
For all Class A, Style Z hookups SW1 & SW2 on the AL800LGK logic board must be closed.
Outputs must be programmed independently (OUT1 - OUT4)
Function
Input to Output
Follower Mode
Temporal
Code 3 Mode
Steady Mode
For the above modes Dip Switch 4 determines which Input controls
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Switch Positions
Function
ON
1, 3,
Amseco Sync
Mode*
Faraday
2, 4
Sync Mode*
Gentex
®
1, 2,
Sync Mode*
3, 4
Gentex is a registered trademark
of Gentex Corporation.
System Sensor
®
Sync Mode*
1, 2, 4
System Sensor is a registered
trademark of Honeywell.
CooperWheelock
®
Sync Mode*
2, 3, 4
CooperWheelock is a
registered trademark of
Cooper Wheelock.
*Note: The AL1002ULADA will only synchronize horns, horn/strobes and strobes that contain synchronization capability.
Contact signal manufacturer for more detailed info. The same synchronization mode must be selected for all outputs.
Note: It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification
appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while
visual notification appliances (strobes) continue to operate.
- 4 -
Output Programming Selection Table:
Switch Positions
Descriptions
ON
OFF
Output follows signal it receives from the corresponding input (i.e. FACP
1
2, 3
Sync module - maintains synchronization of notification appliance circuit).
Enables Temporal Code 3 signal generation output.
3
1, 2
This mode will accept a steady or a pulsing input.
A steady output signal will be generated.
1, 2, 3
This mode will accept steady or pulsing input.
Sync Mode Selection Table:
Descriptions
OFF
This mode is designed to work with the Amseco series of horns, strobes, and horn/
strobes to provide a means of synchronizing the Temporal-coded horns, synchro-
2
nizing the flash timing of the strobe, and silencing the horns of the horn/strobe
4
combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Faraday series of horns, strobes, and horn/
strobes to provide a means of synchronizing the Temporal-coded horns, synchroniz-
1, 3
ing the flash timing of the strobe, and silencing the horns of the horn/strobe combina-
tion over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Gentex
strobes to provide a means of synchronizing the Temporal-coded horns, synchroniz-
ing the flash timing of the strobe, and silencing the horns of the horn/strobe combina-
tion over a two-wire circuit while leaving strobes active.
This mode is designed to work with the System Sensor
horn/strobes to provide a means of synchronizing the Temporal-coded horns, syn-
3
chronizing the one-second flash timing of the strobe, and silencing the horns of the
horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the CooperWheelock series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-coded horns,
1
synchronizing the one-second flash timing of the strobe, and silencing the horns of
the horn/strobe combination over a two-wire circuit while leaving strobes active.
(AL800LGK Board)
Output Dip Switches
series of horns, strobes, and horn/
®
series of horns, strobes, and
®
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
AL1002ULADA