Altronix NetWaySP1BTWP Manual de instalación - Página 4

Navegue en línea o descargue pdf Manual de instalación para Media Converter Altronix NetWaySP1BTWP. Altronix NetWaySP1BTWP 12 páginas. 802.3bt media converter/injector with integral power
También para Altronix NetWaySP1BTWP: Manual de instalación (12 páginas)

Altronix NetWaySP1BTWP Manual de instalación
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes
and authorities having jurisdiction. All units should be installed by a trained service personnel.

Installation:

1. Remove backplane from enclosure prior to drilling. Do not discard hardware.
Note: Make sure that hardware will not interfere with components of the circuit board.
2. Mark and drill desired inlets on the enclosure to facilitate wiring. Maximum NEMA type 4X rated fittings
to be used are 0.5". Follow manufacturer's specifications for the appropriate size opening.
Note: Inlets for conduit fittings should only be made on the bottom of the enclosure.
To facilitate wire entry utilize weather-tight NEMA rated connectors (supplied), bushings, and cable.
3. Clean out the inside of enclosure before remounting circuit boards/backplane.
4. Mounting NEMA4/4X rated enclosure (Enclosure Dimensions, pg. 9, 10):
Wall mount:
Pole Mount:
5. Mount backplane in enclosure with hardware.

Power Connection:

Before powering unit, set input voltage selection switch to proper Input Voltage position
(Fig. 2a, pg. 5, Fig. 3a, pg. 6). Units are factory set for 115VAC.
1. Connect AC power from overcurrent protective device circuit breaker
(20A @ 115VAC, 60Hz or 16A @ 230VAC, 50/60Hz) to the terminals marked [L, N] on power supply
board (Fig. 2, 3, pg. 5, 6). Connect ground lug to earth or green branch wire on backplane (12AWG min.).
Use 14AWG or larger for all power connections (Battery, DC output, AC input).
Keep power-limited wiring separate from non power-limited wiring by utilizing separate knockouts/
inlets. Minimum 0.25" spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing
equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified
service personnel.
3. Battery Backup (if desired): Connect four (4) 12VDC batteries wired in series to terminals marked
[– BAT +] (Fig. 3, pg. 5), carefully observing polarity.
When use of stand-by batteries is desired, they must be lead acid or gel type.
Note: When batteries are not used, a loss of AC will result in the loss of output voltage.

Input/Data Connections:

1. Connect structured cable from port marked [Data Port] on NetWaySP1BT to a PoE midspan/endspan
(Fig. 1, pg. 4).
2. Connect fiber optic cable to a fiber SFP module. Connect the module to the port marked [SFP] on the
NetWaySP1BT. Connect the other end of fiber cable to an SFP module of a remote device.
SFP LED will illuminate indicating data connection (Fig. 1, pg. 4).
3. Using 4-pair CAT5e or higher cable connect PoE load device to be powered to the port marked
[802.3bt Output] on NetWaySP1BT. After authentication and classification have been established,
[PoE Signal] LED will illuminate indicating PoE presence.
IEEE 802.3af, 802.3at and 802.3bt
compliant port rated up to 90W max
Fig. 1
Yellow LED
10/100 Mbps
48VDC to 56VDC
- 4 -

Installation Instructions:

Mount unit in desired location. Mark and drill holes to line up with the top and bottom
hole of the enclosure flange. Secure enclosure with appropriate fasteners (e. g. screws
and anchors; bolts and locking nuts, etc.) that are compatible with mounting surface and
are of sufficient length/construction to ensure a secure mount (Fig. 6, pg. 8).
Refer to Fig. 7 - 11, pg. 8.
48-56VDC
– Input +
-- +
Input
PoE LED indicates PoE present
802.3bt
PoE
Data
Output
Signal
Port
Green LED 1000 Mbps
Ethernet Data Port
One (1) Gb SFP port
for Fiber
Fiber
SFP
Signal
SFP LED Indicates
data connection
NetWaySP1BT Series Powered