ALTUS Du351 Manual del producto - Página 8

Navegue en línea o descargue pdf Manual del producto para Controlador ALTUS Du351. ALTUS Du351 18 páginas.

Duo Series
Doc. Code: CE113100

Analog Inputs

Number of inputs
Input type
Conversion resolution
Terminal block configuration
Configurable parameters
Protections
Updating Time
Note
Updating time: For product revisions before AX, the updating time is 60 ms total.

Voltage Mode

Precision
Crosstalk DC at 100 Hz
Input impedance
Maximum / minimum voltage
without damage
Filtering
Scale
Scale clearance
Notes
Filtering: the time constant value can vary 10% of its nominal value. The maximum deviation of the constant time value is equal
to the sampling rate. Ex: selecting the 140 ms constant time, the maximum time for the current value with filter to have 63% of
the input value is: 140 ms * 110% + 60 ms = 214 ms. The "Disabled" option is available as of version 1.11 of the MT8200.
Counting: the scale limit may be modified by software, the maximum value is 30000.
Scale clearance: defines the percentage over limit scale that can be read by analog inputs. This characteristic can be used to
compensate possible calibration errors of a used sensor.
Altus S. A.
DU350, DU351
4 non insulated (of logic circuit) analog inputs
Voltage: 0 to 10 Vdc
Current: 0 to 20 mA, 4 to 20 mA
12 bits
AV0 – voltage input channel 0
AI0 – current input channel 0
C9 – common for inputs 0 and 1
AV1 –voltage input channel 1
AI1 –current input channel 1
AV2 –voltage input channel 2
AI2 –current input channel 2
C10 –common for inputs 2 and 3
AV3 –voltage input channel 3
AI3 –current input channel 3
Inputs type for each point, voltage or current
Scale limit for each channel, maximum 30000
First order filtering with preset time constants
TVS diode in all analog inputs
1 ms per channel enabled
DU350, DU351
 0.3% of scale limit @ 25°C
0.015% / ºC of the limit scale
- 30 dB
1.1 M
12 Vdc / -0.3 Vdc
Configurable time constant
Disabled, 90 ms, 140 ms, 1 s or 15 s
Range
Counting
0 – 10 V
0 to 30.000
3 %
DU350, DU351
Revision: G
Sensitivity
2.52 mV