QUICKSTART "BASIC" GUIDELINES FOR MODEL 9200 - DIP-SWITCH AND WIRING REFERENCE
This vehicular gate operator is designed for Class III and Class IV applications only and
must never be used in applications serving the general public.
For safety and installation instructions, please refer to the Installation/Owner's manual.
SW 1 DIP-Switches (Right Hand Side)
Switch
Function
Setting
Changes the direction
1
the operator will
open/close the gate.
Auto-Close
2
Timer
Exit Loop Port
Jumper Wire
Needed
3
Output
See Manual
Full Open Input
SW 1
4-OFF
5-OFF
Relay Activation
Upside-Down on Circuit Board.
and
4-OFF
4 and 5
LED Indicator
4-ON
5-OFF
Light Activation
4-ON
Warn Before
6
Operate
7
Reverses Gate
Stops Gate
Quick-Close
8
Timer Override
SW 2 DIP-Switches (Left Hand Side)
Switch
Function
Setting
1
Self-Test
Gate Opens
SW 2
2
Uphill
Upside-Down on Circuit Board.
Gate Opens
3
Downhill
4
Spare
SW 1 - Right 8 Switches
Description
Opening direction
Opening direction
using OFF setting.
using ON setting.
Factory Set Configuration
Auto-close timer is OFF. Manual input required to close gate.
OFF
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.
ON
OFF
The output wired to terminal #4 becomes the output from the loop detector
installed in the EXIT loop port. Plug-in loop detector required for "OFF" function.
ON
Normal Setting. Terminal #4 is a normal full open input for a single gate operator.
Relay activates and LED is ON when the gate is fully open.
Relay activates and LED is ON when the gate is not closed.
5-ON
Relay activates and LED is ON when the gate is opening and open.
Relay activates and LED is ON when the gate is opening and closing.
5-ON
Internal alarm will NOT sound.
OFF
Internal alarm will sound before gate starts and throughout gate's cycle.
ON
OFF
Normal Setting. Input to terminal #6 and/or reverse loops will REVERSE gate
during CLOSE cycle.
ON
Input to terminal #6 and/or reverse loops will STOP gate during CLOSE cycle.
OFF
Normal Setting. Timer will function normally.
ON
Opening gate will stop and begin to close as soon as all reversing inputs (Reverse
loops, photo sensors) are cleared regardless of the distance the gate has opened.
Note: After a DIP-switch setting is changed, power must be turned
OFF and then turned back on for the new setting to take affect.
SW 2 - Left 4 Switches
Description
OFF
Normal Setting. Normal gate operation.
ON
Self-test mode. Operator MUST be disconnected from gate to run self-test.
OFF
Normal Setting. Normal gate operation.
ON
MUST be ON if gate opens UPHILL.
Normal Setting. Normal gate operation.
OFF
ON
MUST be ON if gate opens DOWNHILL.
OFF
Leave in the OFF position.
Important:
Controls intended for user activation must be located at least six (6) feet away from any moving part
of the gate and where the user is prevented from reaching over, under, around or through the gate to operate the
controls. Emergency access controls only accessible by authorized personnel (e.g., fire, police, EMS) may be
placed at any location in the line-of-sight of the gate.
Main Terminal
4404-018
20 19 18 17 16 15 14
Com
Note: All stand-alone and
telephone entry devices
3-Button Control Station Jumper
must use a separate
Jumper Pins 1 & 2 ONLY when
power source.
using a 4-wire control station
to enable stop terminal #9.
SW 1 is Upside-Down on Board
SW 1, Switch 3 MUST be
External Entrapment Protection Devices
ON except for dual
operators or exit loop partial
open applications.
IMPORTANT:
Only 1 monitored Device can be connected to each
input. An OPTIONAL Expansion Kit (sold separately) will allow
connection for additional devices.
IMPORTANT:
Photo sensors must use Normally Closed (NC) contacts with the beam
set for light operate (relay activated when beam is not obstructed). Some
manufacturer's photo sensor contacts are labeled as Normally Open (NO) but their
relay functions the same way as described above. See specific manufacturer's wiring
manual for more information about their specific relay function.
Close Beam
Open Edge
Closed Gate
Telephone Entry
Key Switch
UL 325 DIP-Switches
OPEN Beam
CLOSE Beam
OPEN Edge
CLOSE Edge
Stand-Alone
DIP-switches MUST be turned ON
Keypad
for each device wired to terminal.
Connect ONLY MONITORED Devices
(See Installation/Owner's manual for more information)
Stand-Alone
Card Reader
UL 325 August
2018 Standard
UL 325
DIP-Switches
UL 325 Terminal
6
5
4
3
2
1
3-Button Control Station Jumper
13
12 11
10 9 8
7
6
5 4 3 2 1
Com
Stop
E N
O P
Close
S E
C L O
Open
#1-Com
O P
S T
#2-Fully opens gate.
3-Button Control Station
#1-Com
#2 or #5-Relay
#3-24 volt
250 mamp. max.
Wall
Filler Post If necessary
Open Beam
UL 325 Terminal
#1-24 Volt Power Com
#1-Relay Com
#2 or #5-Relay
#3-24 Volt Power
#5 Terminal Note: Any opening
device connected to terminal #5 will
6
5
4
3
2
1
open the gate to the partial open
setting. External entrapment
protection devices will also open the
gate to the partial open setting. If the
Com
Inherent Reverse Sensor gets
activated during the close cycle, it
N.C.
will always fully open the gate.
N.C.
N.C.
Entrapment Protection must be provided for the
N.C.
N.C.
gate system where the risk of entrapment or
obstruction exists.
The operator will NOT run without one or more
To #4 or #5
monitored type B1 or B2 external entrapment
protection devices in EACH direction of gate
travel (minimum of 2 external devices required).
120 S. Glasgow Avenue
Inglewood, California 90301
U.S.A.
Auxiliary Common
Terminal
Connect any common
wire to these 2 terminals.
Safety Opening Device
3-Wire Radio Receiver
4-Wire Radio Receiver