Arton SPD-3.10 Manual del usuario - Página 2

Navegue en línea o descargue pdf Manual del usuario para Alarma de humo Arton SPD-3.10. Arton SPD-3.10 8 páginas. Optical smoke point detector

1.1 The SPD-3.10 smoke optical point detector is designed to detect smoky fires indoors.
1.2 The detector sets off when small quantities of smoke appear indicating alarm condition and
transmitting alarm signal to a control panel. The detector also has functions of standby mode
indication and checking for proper operation.
1.3 The detector operates with 2-wire and 4-wire fire alarm and fire intruder alarm control
panels all day long. You can connect detectors to a 2-wire CP using B01, B1 bases. You can connect
the detector to a 4-wire CP using B2, B3, B4, and B5 bases. B6, B7, B8, and B9 are end-of-line bases
installed by one at the end of each loop and used in 4-wire loops to control power voltage and
circuit continuity.
1.4 The detector can also be connected to a 4-wire CP using B01, B1 bases as well as MUSH-1,
MUSH-2 and other modules.
1.5 The compatible bases, their features and wiring can be found in Table 1.
Base
B01
B1
B2
B3
B4
B5
B6 (EOL)
B7 (EOL)
B8 (EOL)
B9 (EOL)
Note: «+» denotes the presence of the function, «-» denotes its absence;
2.1 Technical specifications of the SPD-3.10 with B01 base.
2.1.1 Wiring....................................................................................2-wire
2.1.2 Supply voltage range, V...............................................................10 - 30
2.1.3 Standby current consumption, mA...................................................0,10 max
2.1.4 Alarm current consumption, mA ....................................................8 - 30
2.1.5 Internal resistance in alarm mode at 20 mA, Ohm.................................500 max
2.1.6 Reverse current at minus 30 V voltage, μA.............................................5 max
2.1.7 Start-up time, sec.....................................................................................30 max
2.1.8 Dimensions, mm......................................................................................∅85х37
2.1.9 Weight, g.................................................................................................150 g
2.1.10 Operating temperature range, °С..........................................................from - 30 to 55
2.1.11 Meantime-between-failures, h...............................................................60 000 min
2.1.12 Average lifespan, years.........................................................................10 min
2.2 Technical characteristics of the SPD-3.10 detector with the B1-B9 bases.
2.2.1 For technical characteristics of the SPD-3.10 detector with the B1-B9 bases please refer to
the appropriate manuals.
1. FUNCTIONS
Remote
Relay
indicator
-
-
+
-
-
1
-
1
+
1
+
1
-
2
-
2
+
2
+
2

2 TECHNICAL SPECIFICATIONS

Relay
contacts of the
base
-
-
NC
NO
NC
NO
NO, NC
NO, NO
NO, NC
NO, NO
Table 1
Wiring
2-wire
2-wire
4-wire
4-wire
4-wire
4-wire
4-wire
4-wire
4-wire
4-wire