Alula RE614 Manual de inicio rápido - Página 3
Navegue en línea o descargue pdf Manual de inicio rápido para Alarma de humo Alula RE614. Alula RE614 12 páginas. Smoke alarm connect+ compatible
Alarm will return to normal operation.
(Note: this does not reduce the users
fire protection, as a Smoke Alarm in
continuous alarm due to a fault, is useless
and must be silenced – by taking the
Alarm down or as described here. This
procedure has the added benefits that
the user is reminded every 10 minutes by
two short beeps that the Alarm needs to
be replaced and that if the problem clears
the Alarm will return to detecting fire).
1.2.3. Faulty smoke chamber
In the unlikely event of the smoke sensing
chamber becoming defective, the Alarm
will give 2 short beeps with 2 yellow LED
flashes every 48 seconds. The Alarm must
then be replaced.
If it is not convenient to replace it
immediately, pressing the test button will
silence the beeps and stop the yellow
LED flashing for 12 hours. This can be
repeated as required.
2. Location and Positioning
Introduction
Congratulations on purchasing a Smoke
Alarm. You can easily install these Alarms
throughout the property on escape
routes, on each storey, in corridors and in
closed rooms to give warning of fire.
Heat Alarms can be installed in kitchens
and other areas where Smoke Alarms are
unsuitable.
NATIONAL
ASSOCIATION REQUIRED PROTECTION
Smoke Detection. Where required by
applicable laws, codes, or standards
for the specified occupancy, approved
single- and multiple-station Smoke Alarms
shall be installed as follows:
(1) In all sleeping rooms and guest rooms
(2)
Outside of each separate dwelling
unit sleeping area within 6.4 m (21 ft) of
any door to a sleeping room, the distance
measured along a path of travel
(3)
On every level of a dwelling unit,
including basements
(4) On every level of a residential board
and care occupancy (small facility),
including basements and excluding crawl
spaces and unfinished attics
(5) In the living area(s) of a guest suite
(6) In the living area(s) of a residential
board and care occupancy (small facility)
Are More Smoke Alarms Desirable? The
required number of smoke detectors
might not provide reliable early warning
protection for those areas separated by
FIRE
PROTECTION
a door from the areas protected by the
required smoke detectors. For this reason,
it is recommended that the householder
consider the use of additional smoke
detectors for those areas for increased
protection. The additional areas include
the basement, bedrooms, dining room,
furnace room, utility room, and hallways
not protected by the required smoke
detectors. The installation of smoke
detectors in kitchens, attics (finished or
unfinished), or garages is not normally
recommended,
occasionally experience conditions that
can result in improper operation.
The equipment should be wired and
installed in accordance with National
Fire Protection Association's Standard
72, Chapter 11 and National Electric
Code, NFPA 70, Chapter 3. (National
Fire Protection Association, Batterymarch
Park, Quincy, MA 02269).
For Canadian installations wiring methods
shall be in accordance with CSA C22.1,
Canadian Electrical Code, Part I, Safety
Standard
for
Testing and maintenance procedures shall
be in accordance with CAN/ULC-S552,
Standard for the Maintenance and Testing
of Smoke-Alarms.
IMPORTANT!
Specific requirements for Smoke Alarm
installation vary from state to state
and from region to region. Check with
your local Fire Department for current
requirements in your area.
SMOKE ALARMS
Sufficient smoke must enter your Smoke
Alarm before it will respond. Your Smoke
Alarm needs to be within 6.4 metres (21ft)
of the fire to respond quickly. Smoke
Alarms also need to be in positions
where they can be heard throughout the
property, so they can wake you and your
family in time for everyone to escape.
A single Smoke Alarm will give some
protection if it is properly installed, but
most homes will require two or more
(preferably interconnected) to ensure that
a reliable early warning is given. For
recommended protection you should put
individual Smoke Alarms in all rooms
where fire is most likely to break out (apart
from the kitchen and bathroom).
Your first Smoke Alarm should be located
between the sleeping area and the most
likely sources of fire (living room for
example), but it should not be more than
6.4 metres (21ft)from the door to any
3
as
these
locations
Electrical
Installations.