1463H202 Ed.03
GB
Surface temperature controller with 3 relays and 2 probes
Device designed to display, control and regulate cooling generators (manual or automatic
programmable defrosting).
1- Versions and references
MODEL
FUNCTION
COOL: 16 A, 250 V, cos ϕ=1, SPST
AKO-14632
Controller
DEF:
FAN:
2- Technical data
Temperature range:. . . . . . . . . . . . . . . . . . . . . -50.0 ºC to 99.9 ºC (-58.0 ºF to 211 ºF)
Resolution, Set Point and differential: . . . . . . . 0,1 or 1 ºC/ºF configurable by parameter P7
Input for NTC probe: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-149XX
Thermometric accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 ºC
Probe tolerance at 25 ºC: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0,4 ºC
Maximum input power: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 VA
Working ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 ºC to 50 ºC
Storage ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 ºC to 70 ºC
Control device classification:
Independent mounting, with characteristic of automatic operation Type 1.B action, to be
used in a clean situation, logical medium (software) class A and continuous operation.
Degree of contamination 2 on UNE-EN 60730-1
Double insulation between the power supply, the secondary circuit and the relay output.
Allocated pulse temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2500 V
Pressure ball test temperature:
Accessible parts: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC
Parts that position active elements:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 ºC
Voltage and current declared by the EMC tests: . . . . . . . . . . . . . . . . . . . . 207 V, 22 mA
Current of radio jamming supression test: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 mA
3- Installation
The controller should be installed in a place protected from vibrations, water and corrosive
gases, and where ambient temperature does not surpass the value specified in the technical
data.
In order to give a correct reading, the probe should be installed in a place without heat
influences other than the temperature that is to be measured or controlled.
3.1 Fastening
Press down lightly
to open the cover.
Suitable fixing screw-holes for universal
flush-mounting wall box
AKO-14632
1
2
3.2 Connection:
3
The probe and its lead should NEVER be installed in duc-
4
ting along with power, control or power supply wiring.
5
The power supply circuit should be connected with a mini-
mum 2 A, 230 V, switch located close to the unit. Power
supply cables should be H05VV-F 2x0,5 mm
8
2x0,5 mm
9
Section of connecting wires for relays contacts should be
10
2,5 mm
11
12
13
14
4- Funciones del frontal
LED Cool (Compressor)
Permanent: Cooling relay COOL (com-
pressor) energised.
Flashing:
Because of the temperature
detected by Sensor 1 (TEM), the COOL
relay should be energised, but is no due to
a programmed parameter.
LED Fan
Permanent: Fan relay energised.
Flashing:
Because of the temperature
detected by Sensor 2 (DEF), the Fan relay
should be energised, but is no due to a pro-
grammed parameter.
POWER SUPPLY,
RELAY
50/60 Hz
8 A, 250 V, cos ϕ=1, SPDT
230 V~ ±10%
6 A, 250 V, cos ϕ=1, SPST
Detail of fixing screw-holes.
Ø máx. 3,7
35
125,5
.
171
2
2
.
2
.
LED Def
Permanent: Indicates defrost in opera-
tion.
LED Alarm
Permanent: Alarm indicator enabled.
Flashing:
Alarm detected, but display
maintained.
LED DT
Permanent: Indicates last defrost ended
by time.
LED Continuous cycle
Permanent: It indicates that the conti-
nuous cycle is active.
LED ºC
Permanent: Degrees ºC indicator.
Flashing:
Programming phase.
LED ºF
Permanent: Degrees ºF indicator.
Flashing:
Programming phase.
UP KEY
- Press once to cancel the alarms, but they
remain displayed.
- In programming, it makes the displayed
value increase.
- When pressed it displays the help messa-
ge dEF corresponding to the short key
function that it performs.
- When pressed for at least 5 seconds, a
manual defrost is started / stopped with
programmed duration.
DOWN KEY
- Press once to cancel the alarms, but they
remain displayed.
- In programming, it makes the displayed
value reduce.
- When pressed, it displays the help mes-
sage Con corresponding to the function
performed by the key.
- Pressing during 3 seconds,it activates /
deactivates the CONTINUOUS CYCLE
during the time for which it has been
programmed.
RIGHT KEY
- Press once to cancel the alarms, but they
remain displayed.
- In programming, it makes the level value
increase.
- When pressed, it displays the help mes-
sage oFF corresponding to the function
performed by the key.
5- Adjustment and configuration
It should only be programmed or modified by personnel who are fully conversant with the
equipment operation and possibilities.
5.1 Set Point temperature
The factory SET POINT default value is 0.0 ºC.
- Press
key for at least 5 seconds to DISPLAY SET POINT. It displays the CURRENT SET
POINT value and LED ºC or ºF starts flashing.
- Press
or
keys to CHANGE SET POINT into the required value.
- Press
key to ACCEPT THE NEW SET POINT. The display returns to the CURRENT TEM-
PERATURE display status and LED ºC or ºF stops flashing.
- Press the
key to exit the temperature set point without modifying the value.
When PA is displayed, PASSWORD programmed in L5 parameter of tid menu should be
entered to access the CURRENT SET POINT.
- Press
key. 0 will be displayed to ENTER PASSWORD.
- Press
or
keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.
- Press
key to ACCEPT PASSWORD. The CURRENT SET POINT value will be displayed
and it can be already modified.
or H05V-K
5 Sec.
CURRENT
PASSWORD
TEMPERATURE
REQUEST
5.2 Parameters configuration
Level 1
Menus
When the keys
+
shows Pro for 10 seconds. LED ºC or ºF will be flashing, we are in the programming LEVEL
1 MENUS and the first menu "rE" is displayed.
- Press
key to access the next menu and
- Pressing
key, the controller returns to the CURRENT TEMPERATURE display status and
LED ºC or ºF will stop flashing.
When PA is displayed, PASSWORD programmed in L5 of "tid" menu should be entered to
access programming LEVEL 1 MENUS.
- Press
key. 0 will be displayed to ENTER PASSWORD.
- Press
or
keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.
- Press
key to ACCEPT PASSWORD. The first menu "rE" will be displayed.
LED
Cool
LED
Fan
LED
Def
LED
Alarm
LEFT
KEY
DOWN
KEY
- Pressing during 3 seconds it turns off/on
the unit leaving it in STAND-BY. The dis-
play shows oFF when the unit is discon-
nected.
LEFT KEY
- Press once to cancel the alarms, but they
remain displayed.
- Exit programming level.
KEY
- Press once to cancel the alarms, but they
remain displayed.
- In programming, accept the programmed
new value.
- When pressed it displays the help messa-
ge SP corresponding to the function per-
formed by the key.
- When pressed for at least 5 seconds, the
SP Set Point temperature is displayed.
If P2=0 or L5=0
ENTER
DISPLAY
CURRENT
PASSWORD
PASSWORD
SET POINT
are pressed simultaneously for at least 10 seconds, the display
key to return to previous one.
LED DT
LED
ºC
ºC
LED
Continuous
ºF
Cycle
LED
ºF
UP
KEY
SET
KEY
RIGHT
KEY
NEW
SET POINT