AKO 558241 Manual del usuario - Página 7
Navegue en línea o descargue pdf Manual del usuario para Sistema de seguridad AKO 558241. AKO 558241 16 páginas. Gas leak detection + trapped person alarm
Wiring
The wiring between the transmitter / detector / push-button and the station should NEVER be installed in a
conduit alongside power, control or supply cables.
Always disconnect the power supply to carry out wiring.
For disconnection, the power supply circuit must be equipped with a switch of at least 2 A, 230 V, located near
the device. The power supply cable will be H05VV-F or NYM 1x16/3. The section to be used will depend on
current local regulations, but should never be less than 1.5 mm .
Cables for wiring the relay contact should have the relevant section for the device to be connected.
The 120 / 230 V~ wiring must be kept clear of any other external element.
Make sure you have connected the batteries before starting up the device *.
Certain international standards indicate that alarm power supply should originate from a different circuit to
that used for the refrigeration and ventilation system. Be sure to comply with current local regulations.
D
Vac
100 - 240 V~
50/60 Hz
A
RS485
Remote
mute
B
Input 1
Input 2
Only AKO-555242 / 558242
C
Input 4
Input 3
Pre-alarm jumper
Pre-alarm
disabled
Pre-alarm
enabled
RY1
Gas Fail
1
C
2
NO
C
NC
Gas
Trapped
person
system
failure
Remote
Set Hold
RY2
RY3
NC
C
NO
NC
C
NO
Gas
Gas
Pre-Alarm
Alarm
1 / 2
1 / 2
RY4
RY5
NC
C
NO
NC
C
NO
Gas
Gas
Pre-Alarm
Alarm
3 / 4
3 / 4
2
A
*
AKO-558xxx models are not equipped with batteries.
Input x
Input x
7
5552H402 Ed.03
B
C
D
H.E. push-button
15V
Out
Gas transmitter / detector
AKO-575xxx / AKO-5761x
15V
S
GND