Description of parameters and messages
The values in the Def column are factory-set.
Description
Temperature display mode:
0 = Whole in ºC 1 = One decimal in ºC
01
2 = Whole in ºF 3 = One decimal in ºF
02
Probe 1, Enable? (S1) 0=No, 1=Yes
03
Probe 1 calibration (S1)
04
Parameter 03 adjustable by the user? 0=No, 1=Yes
05
Probe 2, Enable? (S2) 0=No, 1=Yes
06
Probe 2 calibration (S2)
07
Parameter 06 adjustable by the user? 0=No, 1=Yes
08
Thermostat relay R1, Enable? 0=No, 1=Yes
09
Thermostat relay R1, Probe selection 0=S1-S2, 1=S1, 2=S2
10
Thermostat relay R1, Operation type 0=Cold, 1=Heat
11
Thermostat relay R1, Set Point
12
Parameter 11 adjustable by the user? 0=No, 1=Yes
13
Thermostat relay R1, Differential (Hysteresis)
14
Parameter 13 adjustable by the user? 0=No, 1=Yes
15
Thermostat relay R1, connection delay or protection
16
Parameter 15 adjustable by the user? 0=No, 1=Yes
17
Thermostat relay R2, Enable? 0=No, 1=Yes
18
Thermostat relay R2, Probe selection 0=S1-S2, 1=S1, 2=S2
19
Thermostat relay R2, Operation type 0=Cold, 1=Heat
20
Thermostat relay R2, Set Point
21
Parameter 20 adjustable by the user? 0=No, 1=Yes
22
Thermostat relay R1, Differential (Hysteresis)
23
Parameter 22 adjustable by the user? 0=No, 1=Yes
24
Thermostat relay R2, connection delay or protection
25
Parameter 24 adjustable by the user? 0=No, 1=Yes
26
Timing relay R1, Enable? 0=No, 1=Yes
27
Timing relay R1, Elapsed time between starts
28
Parameter 27 adjustable by the user? 0=No, 1=Yes
29
Timing relay R1, Duration
30
Parameter 29 adjustable by the user? 0=No, 1=Yes
31
Timing relay R1, Relay status during P29 0=OFF, 1=ON
32
Timing relay R2, Enable? 0=No, 1=Yes
33
Timing relay R2, Elapsed time between starts
34
Parameter 33 adjustable by the user? 0=No, 1=Yes
35
Timing relay R2, Duration
36
Parameter 35 adjustable by the user? 0=No, 1=Yes
37
Timing relay R1, Relay status during P35 0=OFF, 1=ON
38
Parameters transfer 0=disabled,1=send, 2=receive
39
Password to modify the configuration
40
Program version (information)
41
Display without pressing any key
42
Function by pressing UP key
43
Function by pressing UP key during 5"
44
Function by pressing DOWN key
45
Function by pressing DOWN key during 5"
Function by pressing UP + DOWN keys in panel mounting models
46
Function by pressing SET key in DIN rail models
options for parameters 41 to 46
0
Key disabled
1
Display Probe 1 of input (S1)
2
Display Probe 2 of input (S2)
R1 Set Point display
3
Messages
Probe S1 and Probe S2 disabled
---
Probe S1 damaged (open, crossed circuit, temp. > 110ºC or temp. <-55ºC). Assigned
E1
relay OFF.
Probe S2 damaged (open, crossed circuit, temp. > 110ºC or temp. <-55ºC). Assigned
E2
relay OFF.
Flashing:
Probes S1+S2 damaged (open, crossed circuit, temp. > 110ºC or temp. <-
E1+E2
55ºC). Relays R1 and R2 OFF.
Memory error
EE
Maintenance
Clean the unit surface with a soft cloth and soap and water. Do not use abrasive detergents,
petrol, alcohol or solvents.
AKO ELECTROMECÁNICA , S.A.L.
Avda. Roquetes, 30-38
08812
•
Sant Pere de Ribes.
Barcelona
•
Spain.
Tel.: +34 902 333 145
Fax: +34 938 934 054
www.ako.com
PARAMETERS
Values Min. Def. Max.
0
0
(ºC / ºF)
-20.0
0.0
0
0
(ºC / ºF)
-20.0
0.0
0
0
0
0
(ºC / ºF)
-50.0
0.0
0
(ºC / ºF)
-90.0
1.0
0
(min)
0
0
0
0
0
(ºC / ºF)
-50.0
0.0
0
(ºC / ºF)
-90.0
1.0
0
(min.)
0
0
0
(h.)
0
0
0
(min.)
0
0
0
(h.)
0
0
(min.)
0
0
0
0
0
1
0
0
0
0
0
4
R2 Set Point display
5
Start R1 timing
6
Start R2 timing
Accessible parameters adjustment
7
We reserve the right to supply materials that might vary slightly to those described in our Technical Sheets. Updated information is available on our website.
Relays R1 and R2 operation and control
Thermostat relay R1
Operation for HEAT (P10=1)
P13>0
ON
1
3
1
1
OFF
20.0
P11
0
1
Start
1
1
ON
P13<0
20.0
0
1
1
1
1
2
OFF
1
1
P11-P13
P11
99.0
Start
Stop
1
1
90.0
1
1
Operation for COLD (P10=0)
0
120
1
1
P13>0
ON
1
1
1
2
1
1
99.0
OFF
1
1
P11
Stop
90.0
1
1
P13<0
ON
0
120
1
1
0
1
OFF
0
120
P11-P13
P11
1
1
Stop
Start
0
120
1
1
Parameters transfer
0
1
0
1
AKO-14916
0
120
Tabletop server which is connected by
1
1
means of the AKO-80018, 230/12V,
0
120
to the power supply. Permit to transfer
1
1
parameters previously recorded in one
0
1
server AKO-14918, to other panel
0
2
0
126
mounting controllers without these
having to be powered.
1
4
2
7
4
7
0
7
Supply 230V
AKO-80018
3
7
7
7
AKO-14916
Transfer
Panel mounting
models
Technical data
Temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50 to 99 ºC (-58 to 211 ºF)
NTC probe inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-149xx
Controller accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 ºC
Probe tolerance at 25ºC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0.4 ºC
Relay R1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 (4) A*, 250 V, cos j=1, SPST
Relay R2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 A*, 250 V, cos j=1, SPDT
Maximum input power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 VA
Working ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 to 40 ºC
Storage ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 to 70 ºC
Installation category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II según norma CEI 664
3 digits and an optional decimal point when programmed . . . . . . . . . . . . . . . . . . . . . . . .
Double insulation between the power supply, the secondary circuit and the relay output.
* The current specified for each relay is its individual maximum. When more than one relay
is connected, the total current cannot surpass 17,5A (EN61010) or 13A (EN60730).
GB
1472H206 Ed.02
Thermostat relay R2
Operation for HEAT (P19=1)
ON
OFF
P20
P11+P13
Temp.
Start
Stop
ON
P22<0
OFF
P20-P22
P20
Temp.
Start
Stop
Operation for COLD (P19=0)
ON
OFF
P11+P13
P20
Temp.
Start
Stop
P20<0
ON
Temp.
OFF
P20-P22
P20
Stop
Start
AKO-14918
A portable server without supply to
which the parameters programmed in
powered AKO controllers can be
copied. The parameters may then be
transferred from the server to other
identical powered units.
AKO-14918
AKO-14918
Transfer
Power supply
Power supply
ºC
Programming
Programming
Panel mounting or DIN rail models
P22>0
P20+P22
Temp.
Stop
Temp.
P22>0
P20+P22
Temp.
Start
Temp.
AKO-14918
Transfer
ºF
SET