Installation and Operating Manual
for circuit-breakers with residual current trip
of series DFL 8 B SK
Electrical connection
Guide all active conductors (outer cables L1, L2, L3 and the neutral conductor MP/N)
through the switch. The energy flow direction must be observed, i. e. the mains or
consumer unit has to be connected to the lower terminal block. Scrape and grease
aluminium conductors immediately before connection.
Function and area of application
The devices of the DFL 8 B series are circuit-breakers with residual current trip sensi­
tive to all current types for the detection of residual currents of type B. They consist
of a section independent of the mains voltage for the detection of sinusoidal AC and
pulsing DC residual currents with the rated frequency 50 Hz or 60 Hz and a section de­
pendent on the mains voltage for the detection of residual currents in the frequency
range 0 Hz to 100 kHz.
The devices are intended for use in single and multiple phase AC networks. They are
not intended for use in DC networks.
In order to ensure protection across the total frequency range covered in the event
of indirect contact with a maximum contact voltage of 50 V or 25 V respectively, the
earth resistance must be in accordance with the table given below.
Series
maximum touch voltage 25 V
DFL 8 B SK
8.3 Ω
For frequencies > 1 kHz the tripping current for the DFL 8 B SK is up to approx 3 A.
This ensures its insensitivity to high leakage currents in the upper frequency range.
Testing and functional check
The testing of all safety measures on commissioning must be carried out according
to the information in the valid national installation regulations. An insulation test of
the user equipment is to be carried out in accordance with DIN EN 61557-2. This may
only be done when the device is switched off. Insulation testing when the device is
switched on or insulation testing on the input side may lead to incorrect measured
values. A functional inspection of the circuit-breaker with residual current trip itself
is possible with connected mains voltage by pressing the test button T and, as in com­
mercial use (BGV A3), should be carried out at least every six months in the case of
stationary systems and should be repeated every working day in the case of non-
stationary systems.
The green LED signals that the internal operating voltage is sufficient for AC-DC sen­
sitive residual current detection (residual currents of type AC, A and B). If the LED
does not illuminate, then only tripping via type AC and A residual currents is still
guaranteed. The internal supply of the device is via the bottom terminals. At least
two arbitrary conductors must conduct AC voltage of greater than 50 V in order to
guarantee AC-DC sensitive residual current detection.
Important information on operation with electronic equipment
(such as frequency converters, inverters etc.)
1. Electronic equipment and its associated EMC protective provisions, such as e. g.
integrated or in series-connected EMC filters, as well as shielded cables, can give
rise to high capacitive leakage currents.
2. The maximum number of items of electronic equipment connected downstream
of the device is based on the level of leakage currents that occur. Excessive leak­
age currents may lead to undesired tripping in spite of the tripping current fre­
quency response of the device. Relevant information concerning the discharge
currents that are produced can be requested from the manufacturers of the elec­
tronic equipment.
3. During operation with frequency converters long, shielded motor cables may lead
to high discharge currents in the event of the controller release of the frequency
converter, which lead to undesired tripping. If necessary, a sinusoidal output filter
should then be used directly behind the frequency converter (before the shielded
motor cable).
4. According to the instructions, a conventional 3-conductor EMC filter should only
be connected in series with the relevant electronic equipment. So that the filter ef­
fect is not impaired, under no circumstances should further single-phase consum­
ers such as incandescent bulbs be connected on the output side of the EMC filter.
5. As a rule, different clock frequencies (chopper) can be selected in the case of elec­
tronic equipment. In an unfavourable case, the clock frequency may lead to a ten­
dency to oscillation in an upstream EMC filter and therefore to greatly increased
leakage currents, which then result in a tripping of the device. In this case, the
clock frequency must be changed.
3930202 | 11/2013 | Doepke Schaltgeräte GmbH, Stellmacherstraße 11, D-26506 Norden
Application instructions and warnings
The following notes and warnings must be observed in order to ensure safe operation:
1. Installation may only be carried out by an authorised specialist, who is familiar
with the relevant national installation regulations.
2. Without an additional protective housing, the circuit-breaker with residual cur­
rent trip may only be stored and operated in a dry, low-dust environment. An ag­
gressive atmosphere must also be avoided.
3. The user must be made aware of repeat testing using the button T.
4. Using surge current strength CBRs cannot absolutely guarantee to rule out trips
due to leakage currents caused by surge voltage. In cases where an interruption of
the power supply may lead to potential dangers for humans and animals or dam­
age to property, residual current protection should be implemented by means of
increased surge current strength, selective CBRs and upstream surge arresters. In
specific cases, the switching status should be monitored by means of an auxiliary
contactor at the circuit-breaker and an appropriate signalling device.
Guarantee
All professionally installed, unaltered devices are covered by warranty during the
statutory guarantee period from the day of purchase by the end user. The guaran­
tee is not applicable to damage incurred during transport or caused by short-circuit,
overloading or improper use. In the event of defects in workmanship or material,
which are discovered within the guarantee period, the company will provide a repair
or replacement free of charge. The guarantee will be rendered null and void if the
device is opened without authorization.
Technical Data
DFL 8 B SK / SK X / SK V / SK X V
Rated current I n
maximum touch voltage 50 V
16.6 Ω
Rated residual
current I �n
Detection range of residual
current
Rated operat­
ing voltage U e
Rated frequency
min.
operating
voltage
Internal consumption
operating
range of test
circuit
number of poles
Dissipation power P v (typ.)
Short-circuit fuse
Response
times
Non-response
lag time
Rated short­circuit discon­
necting capacity limit I cu
Rated operation short-
circuit disconnecting
capacity I cs
Rated residual current
short­circuit disconnecting
capacity I �m
Surge current strength
Shock resistance
Vibration resistance
Type of protection
Installation position
Supply side
Ambient temperature
1)
DIN VDE 0636, IEC 60269
100 A
125 A
160 A
200 A
standard
0.03 A
series X
adjustable: 0.3 A, 0.5 A, 1.0 A
0 – 100 kHz, 50 or 60 Hz
230/400 V AC
standard
290/500 V AC
series V
50 Hz or 60 Hz
for detec­
tion of
residual
0 V (mains independent)
currents
Type A/AC
for detec­
tion of
residual
50 V AC
currents
Type B
max. 2.5 – 3 W
50 V AC – 400 V AC
standard
series V
50 V AC – 500 V AC
four-pole
35 W
43 W
55 W
72 W
1)
250 A/gG
1 x I �n ≤ 300 ms; 5 x I �n ≤ 40 ms
standard
Range l = 60 – 120 ms
Range ll = 150 – 250 ms
series X
Range lll = 300 – 420 ms
Range llll = 450 – 600 ms
undelayed
standard
Range l = < 60 ms
Range ll = < 150 ms
series X
Range lll = < 300 ms
Range llll = < 450 ms
50 kA at 400/415 V AC
50 kA at 400/415 V AC
50 kA at 400/415 V AC
Proof of the resistance of CBRs to unintended tripping
from surge currents resulting from surge voltages
EN 60947-2:2003 (B.8.6)
20 g / 20 ms duration (IEC 60068-2-27)
1.0 g (f = 2 – 100 Hz) (IEC 60068-2-6)
IP 20
vertical or tilted by 90°
bottom
-25 °C to +70 °C
DFL 8 B SK / SK X / SK V / SK X V
Environmental testing
dry heat
constant
damp heat
cyclic
solid
1 x (4 mm² – 16 mm²); 2 x (4 mm² – 16 mm²)
Cross sections
stranded
1 x (25 mm² – 185 mm²); 2 x (25 mm² – 70 mm²)
Tightening torque
mechanical
Endurance
electrical
Overload
tripping
Design
Residual
requirements
current
tripping
Electromagnetic
compatibility
Weight
1)
DIN VDE 0636, IEC 60269
Auxiliary switch
AC-15: 230 V / 6 A; 400 V / 4 A; 500 V / 2 A
Load rating
DC-13: 24 V / 3 A; 110 V / 0.8 A; 220 V / 0.3 A
Rated operating voltage U e
Rated impulse withstand
voltage U imp
Rated insulation voltage U i
250 A
Cross-sections solid and
1 x (0.75 mm² – 2.5 mm²); 2 x (0.75 mm² – 1.5 mm²)
flexible with ferrules
Characteristics
Auslösestromfrequenzgang / Tripping current frequenzy response
10000
1000
100
10
1
10
Auslösestromfrequenzgang / Tripping current frequenzy response
10000
1000
100
10
10
1
85 W
Auslösestromfrequenzgang / Tripping current frequenzy response
10000
1000
100
10
1
10
Auslösestromfrequenzgang / Tripping current frequenzy response
10000
1000
100
10
1
10
IEC 60068
IEC 60068-2-2
IEC 60068-2-78
IEC 60068-2-30
14 Nm
> 2,000 cycles
> 2,000 cycles
VDE 0660 / EN 60947-2
VDE 0660 / EN 60947-2 Appendix B
EN 60947-2 Appendix J
approx. 5,600 g
230/400 V AC
6 kV
500 V
DF L 8 B S K / 30 mA
100
1000
10000
100000
Frequenz / Frequenzy in Hz
DF L 8 B SK / 300 mA
100
1000
10000
100000
Frequenz / Frequenzy in Hz
DF L 8 B S K / 500 mA
100
1000
10000
100000
Frequenz / Frequenzy in Hz
DF L 8 B S K / 1000 mA
100
1000
10000
100000
Frequenz / Frequenzy in Hz