Doepke Dupline Manual de instrucciones - Página 5
Navegue en línea o descargue pdf Manual de instrucciones para Relés Doepke Dupline. Doepke Dupline 8 páginas. 8-way relay output dsm 8
Doepke
7. General Information
The DSM 8 is a component of the Dupline installation system. It permits the switching of
eight loads, which may be operated on different phases with up to 16 A. However, the
total load may not exceed 80 A.
The switching status of each output is indicated by a LED on the front of the device.
The green LED located in the frontal modular socket indicates that the Dupline bus signal
is functioning properly.
The DSM 8 permits the switching status (ON/OFF) adopted by the outputs in the event
of a bus fault to be preconfigured with the aid of the DHK 1.
8. Coding
With the hand encoder DHK 1 each channel can be assigned any address between A1
and P8 using the modular plug at the front of the DSM 8. The channel allocation is as
follows:
Channel
1..4
Relay output signal 1..4
Functions which are not required should remain uncoded. Coding the DSM 8 can be car-
ried out without supply voltage or Dupline signal. Although it is permanently retained, it
may always be overwritten.
The outputs are configured at the works so that they are switched on if a bus failure oc-
curs. This configuration can also be changed with the DHK 1. If the value "0" is config-
ured, all outputs are switched off in the event of a bus failure; if "1" is set, they are
switched on.
Note:
If you selected „1" (switch on) as priority in case of a bus failure and you left
switching channels uncoded, then the DSM 8 closes the corresponding re-
lays and activates the LED assigned. This is a normal behaviour.
9. Putting into Service
Only an authorized expert is allowed to carry out the installation. When installing, the
connection diagram has to be observed. All conductors that shall be connected have to
be free of voltage. Following table shows the connections:
Terminal
1.1/1.5
Switching ch. 1 (L
2.1/2.5
Switching ch. 2 (L
3.1/3.5
Switching ch. 3 (L
4.1/4.5
Switching ch. 4 (L
3931182/07/08/F - The right to make technical changes reserved!
Operating Instructions
Dupline 8-way Relay Output DSM 8
Description
Description
/L
)
IN
OUT
/L
)
IN
OUT
/L
)
IN
OUT
/L
)
IN
OUT
1- Table of Contents
Channel
5..8
Relay output signal 5..8
Terminal
1.2/1.6
Switching ch. 5 (L
2.2/2.6
Switching ch. 6 (L
3.2/3.6
Switching ch. 7 (L
4.2/4.6
Switching ch. 8 (L
Description
Description
/L
)
IN
OUT
/L
)
IN
OUT
/L
)
IN
OUT
/L
)
IN
OUT
5