Pre-Installation
This appliance must be fitted in accordance
with the current Building Regulations and by
competent registered person.
Health and Safety Precautions Special care
must be taken when installing the stove that the
requirements of the Health and Safety at Work
Act are met.
Note: This appliance is heavy and must be
handled with care. Adequate facilities must be
available for loading, unloading and site handling.
The appliance is supplied fully assembled for a
top flue arrangement.
The door and internal parts can all be removed to
reduce the stove weight during installation.
The paint is soft and vulnerable to marking; refer
to the maintenance section. Clock stoves must be
connected to a suitable chimney. Clock strongly
recommends using a complete and compliant
chimney lining system.
Our stoves contain no asbestos. If there is a
possibility of disturbing any asbestos in the course
of installation then please seek specialist guidance
and use appropriate protective equipment.
Metal Parts When installing or servicing the stove
care should be taken to avoid the possibility of
personal injury.
Ventilation
Document J of the Building Regulations states
that purpose provided ventilation is not required
in England and Wales unless the appliance
nominal rated output is greater than 5kW. Over
5kW 5.5 cm2 of ventilation (550mm2) is required
for every kW output above 5. For example 6.5
kW requires 8.25 cm2 and 8 kW needs 16.5cm2.
In any case, if difficulty in starting the fire or any
excessive fuming is experienced, ventilation must
be put in place as required to eliminate these flue
problems. If a flue draught stabiliser is fitted then
extra ventilation is required. See Document J of
the Building Regulations for detailed guidance
especially in new build properties. A specifically
designed direct outside air connection may be
used with these stoves to provide appropriate
levels of ventilation (significantly in excess of the
above requirements) directly to the stove and
chimney as follows.
6 | Clock Multi Manual
NOTE: As of early 2014 an ADJ vent is still
required even if using an outside air connection.
Always ensure air vents are positioned were they
cannot be blocked
Extractor Fan - Warning There must not be an
extractor fan fitted in the same room as the stove
as this can cause the stove to emit fumes into
the room. If unavoidable the appliance must be
checked with Approved Document (A.D.) 1.21 and
necessary action taken
Action may have to be taken if other heating
appliances are in the same dwelling to make sure
the correct ventilation applies.
Flue Requirements
The chimney must be swept before installation
and checked for soundness and suitability. The
chimney must also be free from cracks and
blockages. If you find the chimney is in a poor
condition then expert advice should be sought.
If the stove was fitted in place of an open fire then
the chimney should be swept one month after
installation to clear any soot falls which may have
occurred due to the difference in combustion
between the stove and the open fire.
The chimney and connecting flue pipe must not
narrow to less than the size of the outlet socket of
the stove at any point. This appliance must not be
used in a shared flue system.
The minimum flue draft is 12 Pascal's at nominal
output.
Minimum flue height required is 5 metres.
The 125mm diameter flue models may be
increased to 150mm diameter.
The 125mm diameter flue should be increased to
150mm in most cases. If the smoke control mode
is engaged a 125mm flue can remain, i.e. Smoke
Tab removed.
If appliance is fitted in an area that has another
flue (mechanical or otherwise) a flue interference
test must be completed and recorded. The
appliance must be checked with reference to ADJ
1.21, and necessary action taken.