Figure 1 Correct installation of flexible gas connection
2
Corrugated Flexible Metallic Hose Assemblies to BS 6501 Part 1 1991 Class 1 Type C
Construction 1 m long - Ambi-Rad Part No. 6500-2
Note Correct installation as shown will allow for approx 150mm of movement due to expansion. This
installation layout is the only method recommended by the institute of Gas Engineers, the
manufacturer and Ambi-Rad Ltd. These instructions must be carried out in accordance with the
relevant provisions of the gas safety (installation and use) regulations 1991 (as amended) and the
manufacturers recommendations.
Corrugated Flexible Metallic Hose Assemblies to BS 6501 Part 1 1991 Class 1 Type C
Construction 600 m long - Ambi-Rad Part No. 6500
Note Correct installation as shown will allow for approx 100mm of movement due to expansion. This
installation layout is the only method recommended by the institute of Gas Engineers, the
manufacturer and Ambi-Rad Ltd. These instructions must be carried out in accordance with the
relevant provisions of the gas safety (installation and use) regulations 1991 (as amended) and the
manufacturers recommendations.