LEAKS
To locate ruptured or corroded tubes or leaking joints between tubes and tubesheet, the fol-
lowing procedure is recommended:
-
Drain the heat exchanger completely of any fluid or moisture.
-
Pressurize the shell side of the unit with fluid (e.g. water, glycol, etc.)
-
Observe the tube joints and tube ends for indication of test fluid leakage
IX. STORAGE & TRANSPORTATION
During transportation of the heat exchangers, ensure that they are not exposed to mechanical
damages. Upon receipt of the heat exchanger, inspect the unit for shipping damages. Notify the
carrier or the sales office immediately in the event that such damages do occur.
Heat exchangers should be stored in a clean, dry, low humidity area away from corrosive envi-
ronments or weather elements (e.g. rain, snow, blowing dust). If the unit is not to be placed in
immediate service, take precautions to prevent rusting or contamination. Heat exchangers that
are out of service for extended periods of time should be protected against corrosion.
CLEANING:
Shell and tube bundle should be flushed out
periodically. If cleaning is necessary, remove
head and bundle to clean inside of shell and
outside of tubes. Replace gaskets if nec essary.
If unit is installed in a hard water area, inside
of tubing can be cleaned as follows:
1.
Break water connections and plug bot-
tom opening.
2.
Fill the tubes wth a solution of 1 part
muriatic acid to 1 O parts of water
and allow to stand for 2 hours:
CAUTION: A longer period may cause
damage to the copper tubing.
3.
Drain off and flush thoroughly wth
clean water.
4.
Re-assemble unit.
Note:
Commercially available cleaners may also be
used.
I.O.M - HEAT EXCHANGERS : SHELL & TUBE, S/W
REPLACEMENT PARTS:
When ordering replacement parts specify:
1.
Complete Model Number
2.
Date of Manufacture
3.
Special Materials if Required
Normally, the only replacement parts required
woud be:
1 - Tube Bundle
1 - Set of Gaskets
Replacement heads are also available if re-