POWER CONNECTOR AND INDICATOR LED's
Power Connector
The SD17060B operates on 115Vac. If 230Vac is the only power available, consider using one
GND
of the 230Vac drivers available from AMCI. Information on these drivers can be found on our
website, http://www.amci.com. If this is not an option, a step-down transformer must be
N
installed to power the SD17060B. The transformer must have a minimum power rating of 800
L
VA.
AC POWER
The SD17060B must be grounded for proper operation. Grounding is accomplished with the
95 – 132 V
AC
GND pin on the power connector, and through proper bonding to the enclosure. Power con-
50/60 Hz
nections should be tight. Loose connections may lead to arcing which will heat the connector.
Phoenix Contact specifies a tightening torque of 4.4 to 5.4 lb-in (0.5 to 0.6 nM)
Indicator LED's
The SD17060B has two indicator LED's.
STEP/FAULT
Green:
Driver Operational
Flashing Green:
Red:
Driver Fault (The Over Temperature and Over Current faults can be cleared with the Disable
Input.)
1) Over Temperature Fault: The heatsink temperature exceeds 90°C (195°F)
2) Over Current Fault: Generally, a short exists somewhere in the system. This can be a short in the
motor or in the driver itself.
A)Phase–Phase Short:There is an electrical short between the two motor windings. The short
B)Phase–Ground Short:One of the motor's windings is shorted to earth ground. (The EARTH GND
C)Back EMF:In applications with large motors and high deceleration rates, back-EMF generated by
3) Interlock Fault: The two Interlock Terminals on the motor connector are not connected with a short
jumper.
Flashing Red:
motor current is set to zero.
Flashing Red/Green @ 1Hz:
driver was ready for them. The driver was disabled, in a fault condition, or had not completed its initial-
ization sequence on power up or reset. The stepper motor position will be invalid. The motor is not dis-
abled and can still be driven. While there is motion, the LED will flash at approximately 4 Hz.
CURRENT LOOP GAIN:
5 all turned off) When set to AutoID, the driver will determine the parameters of the attached motor on
power up and will flash the Step/Fault LED green the number of times that the parameter should be set
to. Flashing red indicates a problem with the motor wiring or the motor current is set to zero. Further
information can be found in the next section of the manual, Verifying System Setup.
Power
Green:
Power is applied to the driver in the range of 95 or 132 Vac.
20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
Driver Operational, Receiving Pulses
exists in the motor cable or in the motor itself.
terminal of the Motor Connector is used as the reference point.) The fault
can be in the motor cable or in the motor itself.
the motor may also cause this fault.
Current Loop Gain AUTOID Error. There is a problem with the motor wiring or the
Step Violation: The indexer sent step pulses to the SD17060B before the
This LED is also used when the Current Loop Gain is set to AutoID. (SB2:1-
13