Flomatic DHC-100D Manuel de configuration et d'utilisation - Page 11
Parcourez en ligne ou téléchargez le pdf Manuel de configuration et d'utilisation pour {nom_de_la_catégorie} Flomatic DHC-100D. Flomatic DHC-100D 15 pages. Digital high-resolution controller
Flomatic Smart Card
Model FDHC-100 (Digital High-Resolution Controller)
Configuration and Operation Manual
POWER REQUIREMENTS
FDHC-100, FDHC-100C: 117VAC ±10%, 50/60 Hz
FDHC-100A, FDHC-100D: 234VAC ±10%, 50/60 Hz
FDHC-100B, FDHC-100E: 24VAC ±10%, 50/60 Hz
12 VA typical (not including output load)
Fuse Type: 5A TR5 Slo-Blo (replaceable)
COMMAND SIGNAL INPUT
Input Impedance
20K ohms (1-5 VDC, 0-5 VDC, 0-10 VDC Input)
251 ohms ±1% (4-20 mA Input)
Loss of Command threshold
< 0.75V or > 5.5V (1-5 VDC input)
< 3mA or > 22mA (4-20mA input)
FEEDBACK SIGNAL INPUT
Input Voltage: 0 to 2.5 VDC
External Feedback Potentiometer: 1K ohm
POWER SUPPLY OUTPUTS
+15V OUT (J2-8): 125mA maximum (not including option module)
+5V OUT (J2-7): 5mA maximum
NOTE:
Do not
connect these outputs to other power supplies.
AC MOTOR OUTPUTS
Off-state Leakage Current: <15mA
Maximum Load Current @ 60°C: 5A
ENVIRONMENTAL
Operating Temperature Range: 0 °C to 60 °C
Storage Temperature Range: -40 °C to 85 °C
Relative Humidity Range: 0 to 90 % (non-condensing)
CE CERTIFICATION
EN55011, Class A RF Emission
EN61000-4-2 Electrostatic Discharge (ESD)
EN61000-4-3 Radiated RF Immunity (10V/m)*
EN61000-4-4 Electrical Fast Transient (EFT)
EN61000-4-5 Surge Pulse (Class 3 with less than 10m cable)
EN61000-4-6 Conducted RF Immunity (3V)
EN61000-4-11 Brown Out / Black Out
* The unit exhibits a particular sensitivity at 137MHz. Installations suspected of having a strong exposure near the specified
limit in the range of 132 MHz to 142 MHz can increase immunity by installing a clamp-on ferrite (250 ohms or more at 100MHz)
around the I/O cable(s). A Steward 28A2029-0A2 ferrite or equivalent is recommended.
Flomatic Corporation
Glens Falls, NY 12801
Phone (518) 761-9797
Fax (518) 761-9798
TM
SPECIFICATIONS
(FDHC-100D only)
FDHC-100 Configuration & Operation Man. Rev 0
August 16, 2010
11 of 14