"-":4-20mA output terminal
"+":15-24V power "+" terminal
"+" Connect with +24V external power, current output from "-" to computer/sample
resistance of the display. After flow through some load resistance like sample
resistance,then back to power "-".
2.Auxiliary Wire(3-digit small terminal)
4-20mA current output type with no auxiliary small terminals.
Fout: Pulse output terminal
When "+" "-" connect with external power then work,pulse output from "Fout".
The three-wire near main terminal are pulse output switch.
If connect to the outside F0,there will be pulse output.
If connect to the inside,then no pulse output.
For two wire current type,only insert outside while testing.
If use current,must insert inside NC to disconnect pulse output. Or else,the current
will not be accuracy.
This pulse is origin pulse without any modify,usually use while doing calibration;
Output signal is the open-collector output include 2K7 pull-up resistor.
System wiring please refer to the appendix "TB3WE three wire" and "TB2WE
Two Wire".

3.2 Local LCD Operation Instruction

3.2.1 User Menu Operation

(1)Working Menu
After power-on,meter will be self-checking first,after then it will enter into
LCD(figure 1 )working display status.
Chart 1 TB2/3WE working screen (Figure One)