American Sensor SA360 Manuel
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} American Sensor SA360. American Sensor SA360 1 pages. Ionization type model - 120 vac hardwire
Également pour American Sensor SA360 : Manuel de l'utilisateur (2 pages)
SMOKE ALARM MANUAL
Ionization Type Model - 120 VAC Hardwire
Model SA 360 -
€
Professional Multi-Location Model 120 Volt
A C H ardwire Smoke A larm. T his model is interconnectable with
up to 11 other units.
I mportant information about your smoke alarm
€ Install alarms outside of every bedroom area and on every floor of
your home. Please refer to Section 3 • W here to Locate Smoke
A larmsŽ for details.
€ Test the alarm weekly by pressing and holding the test button for
up to 20 seconds until the alarm sounds.
€ T he model described in this manual is designed for single
family residences, including homes and apartments rather than
commercial or industrial use.
Smoke A larm Safety Features
€ D ual-I onization C hambers - A dvanced design responds to visible
or invisible particles of combustion (smoke) to sense fires in their
earliest stages. C ompensates for changes in humidity and
temperature to virtually eliminate • nuisanceŽ alarms caused by
normal atmospheric changes in the home.
€ Operating L ight (L E D ) - A continuous green light located behind
the slotted case indicates the smoke alarm is receiving A C power.
€ I nterconnection - Interconnection facilities for up to 11 other
units, using only three wires, including A C power. W hen one
alarm sounds, all properly interconnected smoke alarms follow.
N OT E: Interconnect only with the models specified in Section 6.
€ A larm Source I ndicator - T he red operating light in the unit
originating the alarm will flash rapidly in the event of an alarm.
W ith interconnected units, this feature allows for an easy check to
determine the originator.
€ L ocking K ey - T he auxiliary locking key provided can be used to
lock the smoke alarm to the mounting plate. T his helps to reduce
the risk of unauthorized removal.
€ Sensitivity T est B utton - Test sensitivity, as well as circuitry and
horn. W ith interconnected units, activating test button on one
unit will cause all properly interconnected units to sound. A n
important and convenient check of system integrity.
€ Quick D isconnect Power C onnector - For easy installation,
connect the wires separately from the unit and then plug into the
back of the unit.
€ D etachable Mounting Plate - For easily securing the alarm to the
junction box.
CONTENTS OF THIS MANUAL
1. C A PA BILIT IES A N D LIMITAT ION S OF SMOK E A LA R MS
2. SA FET Y T IPS
3. W H ER E T O LOC AT E SMOK E A LA R MS
4. N FPA R EC OMMEN DAT ION S
5. LOC AT ION S T O AV OID
6. IN STA LLAT ION A N D T EST IN G
7. MA IN T EN A N C E A N D T R OU BLESH OOT IN G
8. LIMIT ED WA R R A N T Y
9. OT H ER A MER IC A N SEN SOR S PR ODU C T S
1. CAPABILITIES AND LIMITATIONS OF SMOKE ALARMS
A merican Sensors smoke alarms are designed to provide early
warning of fire and smoke at reasonable cost. Early warning can
mean the difference between a safe escape and no escape at all.
W hile smoke alarms can provide invaluable protection for you and
your family, they do have limitations.
€ Smoke alarms cannot work without power. Battery operated
alarms will not work without proper batteries, with dead batteries
or if batteries are not properly installed. A C powered alarms will
not work if their A C power supply is cut off by an electrical fire,
an open fuse, a circuit breaker or any other reason.
If you are concerned about the reliability of either batteries or your
A C power supply for any of the above reasons, you should install
in your home both A C and battery powered smoke alarms for
added security. A merican Sensors also offers the SA 379 model
which is A C powered with battery back-up.
€ Smoke alarms are incapable of sounding the alarm until smoke
reaches the sensing chamber. A nything preventing smoke from
reaching the alarm may delay or prevent an alarm. A smoke alarm
cannot detect fire in the walls, chimney or roof unless and until a
significant amount of smoke reaches the alarm. A closed door may
prevent smoke from reaching an alarm on the other side of the
door. A smoke alarm may not sense a fire on another floor of a
home. For example, a basement smoke alarm may not detect a fire
which started on the first or second floor.
€ Smoke alarms may not be heard. T he loudness of the horn in
your alarm meets current standards. H owever, the sound may be
blocked by distance, closed doors, or ambient noise such as traffic
or a stereo. Smoke alarms may not be heard by persons who are
hard of hearing.
For these reasons, a smoke alarm should be installed in every
room or at least on every level of your home. A merican Sensors
recommends that hardwire A C Powered smoke alarms be
interconnected, so that one alarm will trigger all other alarms to
sound their alarms.
€ Smoke alarms are not fool-proof. Smoke alarms may not always
sense every kind of fire. T hey cannot be expected to sense fires
caused by carelessness or by safety hazards. T hey may not give
early warning of fast growing fires caused by smoking in bed,
violent explosions, escaping gas, improper storage of flammable
materials, overloaded electrical circuits, natural causes such as
lightning, children playing with matches, or arson.
€ Smoke alarms are not substitutes for property, disability, life or
other insurance of any kind. H ome owners and renters should
continue to insure their lives and property. C onsult your insurance
agent.
€ Smoke alarms have limited lives. One or more of the many
components could fail at any time. T herefore, test your smoke
alarm weekly. C lean and take care of it as described in this
manual. R epair or replace the smoke alarm when it fails to test
properly. Your smoke alarm should be replaced if it is ten years
old.
€
I onization Technology vs.
Photoelectronic T echnology
Smoke A larms
T here are two different types of smoke alarm technology
currently in general use: ionization and photoelectronic. W hile
both types of technology are suitable for general residential use,
an ionization alarm will normally respond faster to fast flaming
fires, while a photoelectronic alarm may be more sensitive to
detecting slow smoldering fires. Because home fires develop in
different ways and are often unpredictable in their growth, it is
impossible to predict which type of alarm will provide the earliest
warning. For best home protection install at least one
photoelectronic and one ionization smoke alarm on each level of
your home. Model SA 360 is an ionization type smoke alarm.
A photoelectronic smoke alarm senses smoke using an electronic
photo receptor to sense the scattering of light by smoke particles.
2. SAFETY TIPS
Properly installed and maintained smoke alarms are an essential part
of a good home fire safety program. Your fire safety program should
also include a review of fire hazards and the elimination of
dangerous conditions whenever possible. C onsider the following tips:
€ U se smoking materials properly. N ever smoke in bed.
€ K eep matches and cigarette lighters away from children.
€ Store flammable materials in proper containers. N ever use them
near an open flame or sparks.
€ K eep electrical appliances in good condition. Do not overload
electrical circuits.
€ K eep stoves, fireplaces, chimneys, and barbecue grills grease free.
Make sure they are properly installed and away from any
combustible materials.
€ K eep portable heaters and open flames such as candles away from
combustible material.
€ Do not allow rubbish to accumulate.
€ K eep a supply of extra batteries on hand for your battery powered
smoke alarms.
€ Do not stand too close to the alarm when the unit is in alarm as the
loud horn could damage your hearing.
N ever disconnect the battery or the A C power on any type of smoke
alarm to silence a nuisance alarm. C lear the area of smoke by opening
doors and windows or fanning the smoke away.
WAR NING
!
Most important, when fire strikes, a prepared
and practiced escape plan can make the difference between life and
death. D evelop an escape plan and practice it with the entire family,
including small children.
€ Ensure all family members are familiarized with the alarm signal.
€ Prepare an escape plan. Draw a Floor Plan of Your H ome and
determine two exits from each room. T here should be a way to get
out of each bedroom without opening the door.
€ H ave Fire Drills Often. Practice your Escape and BE PR EPA R ED.
€ Decide on a meeting place at a safe distance from your home.
IN CASE OF FIRE
€ Don•t waste time collecting possessions after a fire starts.
€ A rouse all occupants and leave the building. Your most valuable
possession is your life.
€ Doors can mean escape or death. N ever open doors without first
checking for heat. Test them with your hands, if they feel warm, fire
may be walled up behind them - leave closed and find another
escape route.
€ C all the fire department from OU T SIDE the building.
€ If trapped inside, stay close to the floor, cover mouth with cloth,
conserve breath as you crawl to safety.
€ K eep all doors and windows closed except for escape purposes.
€ N EV ER re-enter a burning building.
€ K eep your family in a pre-arranged meeting place after your escape.
Your local fire department may be able to offer you additional ideas
for safety and escape plans in the home.
3a. WHERE TO LOCATE SMOKE ALARMS
A s a minimum, smoke alarms should be located between sleeping
areas and potential sources of fire such as a kitchen, heated garage or
basement. In single storey homes with one sleeping area, an alarm
should be installed in the hallway outside the bedrooms (see Figure
1). In single storey homes with two separate sleeping areas, a
minimum of two alarms are required, one outside each sleeping area
(see Figure 2). In multi-level or split-level homes, as a minimum, an
alarm should be installed outside each sleeping area, in the basement
and at every level of the home (see Figure 3).
€ In every room of your home (except the bathroom): R esearch
indicates that substantial increases in warning time can be obtained
with each properly installed, additional alarm.
€ In bedrooms: In anticipation of fires originating within these rooms,
caused by faulty wiring, lamps, appliances, smoking or other hazards.
€ In hallways: A t a distance no greater than 13 feet (4 meters) from
the farthest wall and no greater than 26 feet (8 meters) from the
next alarm.
€ In the center of a room or hallway: A s it is impossible to predict the
source of a fire. If it is necessary to place the alarm on a wall, always
locate the top of the smoke alarm 4-6 inches (10-15 cm) from the
ceiling.
€ A s needed: To compensate for closed doors and other obstacles that
may interfere with the path of smoke to an alarm. T hey may also
prevent occupants on one side of a closed door from hearing a alarm
on the other side of the door.
€ Model SA 360 - Professional Multi-Location model can be located
in any area of the home.
R EA D • C A PA BILIT IES A N D LIMITAT ION S OF SMOK E
A LA R MSŽ in Section 1 of this manual.
Your local fire department or insurance company may be able to give
you further advice on the best smoke alarm locations in your home.
C all them and ask.
Dining
K itchen
B edroom B edroom
Dining
K itchen
B edroom
T V R oom
Living R oom
B edroom
Living R oom
B edroom
B edroom
Hall
B edroom
B edroom
F igure 2
F igure 1
Living
R oom
Hall
Kitchen
S moke alarms for limited protection
F igure 3
Additional s moke alarms for better coverage
B asement
Furnace
T hese diagrams show smoke alarm
locations as recommended.
3b. WHERE TO LOCATE SMOKE ALARMS IN MOBILE HOMES
N OT E : Power supply must be 120 V olts A C for model SA 360.
In mobile homes built after 1978 locate the smoke alarm as
described above.
Older mobile homes may have little or no insulation compared to
the ones built post 1978. T hese uninsulated exteriors can disrupt
airflow around the smoke alarm in hotter or colder weather. L ocate
the alarm only on interior walls 4Ž to 6Ž (10 to 15 cm) from ceiling
1. if you own an older mobile home or 2. if you notice the exterior
walls and/or ceiling are noticeably cold or warm or 3. if you are
uncertain about the quality of insulation.
R egardless of the age of the mobile home, locate alarms throughout
to ensure maximum protection. Follow the location instructions in
this manual.
4. NFPA RECOMMENDATIONS
For your information, the N ational Fire Protection A ssociation•s
Standard 72 reads as follows:
2-2.1.1.1
Smoke alarms shall be installed outside of each separate sleeping
area in the immediate vicinity of the bedrooms and on each
additional storey of the family living unit, including basements and
excluding crawl spaces and unfinished attics. In new construction a
smoke alarm also shall be installed in each sleeping room.
A -2.5.2.1 Smoke Detection- A re More Smoke A larms Desirable? T he
required number of smoke alarms might not provide reliable early
warning protection for those areas separated by a door from the
areas protected by the required smoke alarms. For this reason, it is
recommended that the householder consider the use of additional
smoke alarms for those areas for increased protection. T he
additional areas include the basement, bedrooms, dining room,
furnace room, utility room, and hallways not protected by the
required smoke alarms. T he installation of smoke alarms in
kitchens, attics (finished or unfinished), or garages is not
normally recommended, as these locations occasionally
experience conditions that can result in improper operation.
5. LOCATIONS TO AVOID
Avoid locations where smoke may not reach the alarm in time to
provide early warning, or where the alarm may not be effective.
D O N OT PL A C E SMOK E A L A R MS:
€ I n turbulent air from fans, doors, windows, etc. T he rapid air
movement may prevent combustion particles from entering the
alarm.
€ I n dead air spaces such as at the peak of an • A Ž frame ceiling.
• Dead airŽ at the top may prevent smoke from reaching the alarm
in time to provide early warning. In rooms with simple sloped,
peaked or gabled ceilings, install smoke alarms on the ceiling
3 feet (90 cm) from the highest point of the ceiling.
N ote: For complex ceiling structures, consult a safety expert for
the number of alarms required and the best locations.
€ I n very hot or cold areas where the temperature exceeds 100
F
0
(38
0
C ) or falls below 40
0
F (5
0
C ).
€ Less than 6 inches (15 cm) from the wall when mounted on the
ceiling.
N uisance alarms could result when smoke alarms are located where
interference may occur with the sensing chamber. T o avoid nuisance
alarms, D O N OT place smoke alarms:
€ I n high humidity areas such as bathrooms and attics. Place smoke
alarms at least 10 feet (3 meters) away from bathrooms.
€ I n insect-infested areas.
€ I n poorly ventilated kitchens or garages.
€ I n very dusty and dirty areas.
€ N ear fluorescent lights. Place smoke alarms at least 5 feet
(1.5 meters) from fluorescent lights.
T his smoke alarm is suitable for residential
WAR NING
!
use. It is not to be connected to a commercial
or industrial fire alarm panel.
6. INSTALLATION AND TESTING
T his model has an optional Locking K ey to better secure the alarm
to inhibit unauthorized removal. If securing the alarm is a concern,
remove and save the • Locking K eyŽ from the back plate with needle
nosed pliers before installing the alarm. See point 12 in this section
for more details on this feature.
A . I nstallation
Mount to any standard or rectangular junction box with a minimum
depth of 1 inch (2.5 cm). 120V A C , 55mA operation.
WA R N IN G : W iring should only be installed by a licensed
electrician in accordance with the N ational Electrical C ode and
local codes.
WA R N IN G : T he circuit used to power the smoke alarm must be a
24 hour voltage circuit that cannot be turned off by a switch or a
ground fault interrupter. It is highly recommended that smoke alarms
be wired on a separate circuit (one with no other lights or
appliances) to ensure maximum reliability of A C power supply. For
installation of smoke alarms in Dwelling U nits, it is important to
follow the N ational Electrical C ode and local codes.
1. Electricity must be turned off at service entrance before
beginning installation to prevent electrical shock or equipment
damage.
2. Location must comply with applicable building codes.
3. Install a junction box where you plan to install the alarm. U se
standard 14 gauge wire.
4. C onnect black and white wires color to color from power
connector to A C power leads.
5. For multiple station application use the orange wire to
interconnect. If unit is not to be interconnected, cap unused
wire. N OT E: T he SA 360 is interconnectable with up to 11
other units.
6. Loosen or remove screws from junction box.
7. A ttach flat side of mounting plate and tighten screws to fit
snugly against the junction box and ceiling or wall.
S moke alarm
quick dis connect
power connector
mounting plate
paper gas ket (not s hown-fits in between)
8. Bring power connector through center opening.
9. Slip the paper gasket supplied with the alarm over the power
connector and then onto the mounting plate so that the four
plastic tabs on the mounting plate will hold the gasket in place.
T he gasket will prevent downward air currents from entering the
smoke alarm through holes in the back of the alarm, unless
blocked off, downward air currents could prevent smoke from
entering the alarm. WA R N I N G : IT IS IMPER AT IV E T H AT
YOU IN SERT T H E G A SK ET W H EN IN STA LLIN G YOU R
SMOK E A LA R M.
10. A lign the plug area on the smoke alarm with the cutout in the
gasket and place the smoke alarm on the mounting plate, turn
clockwise to fasten it to the mounting plate.
11. Plug wire connector into the back of the alarm.
12. If auxiliary lock is desired, insert the Locking K ey into the slot
in the base of the alarm. Locking K ey should • clickŽ into
position and be flush with the alarm housing. C A U T ION : Do
not attempt to remove alarm without first removing the Locking
K ey. If the key is not first removed, damage may result. To
remove, use a screwdriver and gently pry the Locking K ey loose.
To Us e Optional Locking K ey-
R emove from mounting plate with needle nos ed pliers and ins ert in hous ing
E
13. Test alarm operation after installation in accordance with
• Operation: H ow to TestŽ instructions.
B LAC K
120V AC , 60Hz
WHIT E
MODEL SA 360
Outlet B ox
C ap Unus ed Wire
120VA C Dual-Ionization
T wis t C onnectors
Interconnectable
C eiling
Smoke A larm
Mounting P late
S upplied G as ket Mus t B e
Ins talled In Mounting P late
S moke Alarm
Quick Dis connect
P ower C onnector
S ING L E S TAT ION
B LAC K 120V AC , 60Hz
WHIT E
OR ANG E Interconnect
MULT IP L E S TAT ION
N ote: Maximum interconnect wiring length is 150 feet (50 meters).
I MPOR T A N T : T he SA 360 is not interconnectable with any other
model produced by another manufacturer. T he SA 360 may be
interconnected only with the following U nderwriters• Laboratories
Inc. listed smoke alarm models:
A merican Sensors
SA 379
A merican Sensors
SA 360
A SI Electronics (A merican Sensors)
ESA 5010/ESA 5011
Dicon Safety Products Inc.
670L/LR
Dicon Safety Products Inc.
370LBX
N ote: T his equipment should be installed in accordance with the
N ational Fire Protection A ssociation Standard 72. ( N ational Fire
Protection A ssociation, Batterymarch Park, Quincy, MA 02269) .
B . T esting A fter I nstallation
1. C heck to see that the green • POW ER ON Ž light is on. T he
• POW ER ON Ž light is visible behind the slotted case and
confirms that the smoke alarm is receiving A C power.
2. Press and hold the test button until the alarm sounds. N OT E: It
may be necessary to press the test button for up to 20 seconds for
an alarm to sound. A n alarm is indicated by 3 loud beeps
repeating every 5 seconds. A larm may continue to sound for up
to 10 seconds after button is released.
3. A t least once a week, press the test button and hold until the
alarm sounds, then release.
N OT E: Multiple Station Only:
4. Test each alarm separately in the system.
5. Determine that the initiating alarm triggers other alarms in the
system.
7. MAINTENANCE & TROUBLESHOOTING
T EST T H E A LA R M W EEK LY. VA C U U M EV ERY SIX MON T H S.
Your smoke alarm should be cleaned every six months to help keep
the unit working efficiently. R EMOV E POW ER T O A LA R M.
G ently vacuum through the vents of the alarm with a soft brush
attachment. K eep vacuum nozzle from touching the unit.
R E-ESTA BLISH POW ER T O A LA R M.
Problems may be indicated by the following:
1. T he alarm does not sound upon pressing the test button.
2. T he green operating light does not remain steadily on when unit
is A C powered.
3. T he red operating light remains steadily on or off. (i.e. does not
flash once every 45 seconds, when the unit is not in alarm).
Try the following:
1. Inspect breaker or fuse in power circuit to alarm.
2. G ently vacuum as recommended above.
3. C all an electrician to inspect house wiring and connection to
alarms.
If these procedures do not correct the problem, do N OT attempt
repairs. If the smoke alarm is within warranty period and terms,
indicate the nature of the problem and return the unit with proof of
purchase to the point of purchase, distributor or manufacturer. See
below for instructions. U nits beyond warranty cannot be
economically repaired.
FA L SE A L A R MS:
A bnormal air conditions may cause the highly sensitive smoke alarm
to give a • falseŽ alarm. If no fire is apparent, ventilate the room
and/or blow fresh air into the unit until the alarm stops. Once
cleared, the smoke alarm will automatically reset.
DO N OT DISC ON N EC T T H E A C POW ER SU PPLY.
Dust can lead to excess sensitivity. Vacuum as recommended above.
DO N OT PA IN T T H E U N IT.
8. LIMITED WARRANTY
Your A merican Sensors SA 360 smoke alarm is warranted for ten
years from the date of purchase against defect in material and
workmanship. U nits returned to Dicon G lobal Inc.
with proof of purchase date during this period as a result of such
defects will be repaired, or replaced at Dicon G lobal Inc.s
.
option, without charge. T his warranty only covers defects in
•
material or workmanship in normal residential use. T his warranty
does not cover damage resulting from negligent handling, misuse, or
lack of reasonable care. T his warranty is in lieu of any other
warranty either expressed or implied.
DIC ON G LOBA L IN C . SH A LL H A V E N O
LIA BILIT Y FO R A N Y PER SON A L IN JU RY O R PR OPERT Y
DA MA G E, O R A N Y SPEC IA L IN C IDEN TA L, C ON T IN G EN T
O R C ON SEQU EN T IA L DA MA G E OF A N Y K IN D R ESU LT IN G
FR OM A FIR E. T H E EXC LU SIV E R EMEDY FO R BR EA C H OF
T H E LIMIT ED WA R R A N T Y C ON TA IN ED H ER EIN IS T H E
R EPA IR O R R EPLA C EMEN T OF T H E DEFEC T IV E PR ODU C T
AT DIC ON G LOBA L IN C .S OPT ION IN N O
C A SE SH A LL DIC ON G LOBA L IN C .S
LIA BILIT Y U N DER A N Y OT H ER R EMEDY PR ESC R IBED BY
LAW EXC EED T H E PU R C H A SE PR IC E. YOU R SMOK E
A LA R M IS N OT A SU BST IT U T E FO R PR OPERT Y,
DISA BILIT Y, LIFE O R OT H ER IN SU R A N C E OF A N Y K IN D.
A PPR OPR IAT E C OV ER A G E IS YOU R R ESPON SIBILIT Y.
C ON SU LT YOU R IN SU R A N C E A G EN T.
T his warranty gives you specific legal rights and you may have other
rights which may vary from state to state.
U nits may be returned to point of purchase according to
retailers exchange / return policy. Or call 1-800-387-4219, for
shipping instructions and a returned goods authorization number
• R G A Ž number, to return to Dicon G lobal Inc.
R eturned goods must be shipped prepaid. A cheque for $5.00 is
also required for return postage. Please mark the • R G A Ž number
on the exterior of your package. Date code located on back of smoke
alarm.
Dic on G lobal Inc .
20 S teelcas e R oad, Unit 3
Markham, Ontario,
C anada L3R 1B 2
9. AMERICAN SENSORS PRODUCTS
A merican Sensors offers a complete line of smoke alarms. Select
from this group of quality products to ensure your home is fully
protected in case of fire.
A ME R I C A N SE N SOR S SMOK E A L A R MS
Smoke A larm
Model
D escription
Power Source
T echnology
Ionization
SA 310
Basic Model
9V Battery
G eneral Purpose Model
SA 320
9V Battery
Ionization
with A larm-Pause
®
Feature
H all and Stairways Model
2-9V Batteries
Ionization
SA 358
with Emergency Light
Extended Life
Extended Life
Ionization
Multi-Location with
Battery with
SA 500
A larm-Pause
Model
®
3 Year Warranty
Long Life Multi-
Long Life Lithium
SA 900
Location with
battery with 10
Ionization
A larm-Pause
Model
®
year warranty
Professional H ardwire
SA 360
120 Volt A C
Multi-Location Model
Ionization
Professional H ardwire
120 Volt A C with
with Battery Back-U p
SA 379
9 Volt Back-U p
Ionization
and A larm-Pause
®
Battery
Model
A ME R I C A N SE N SOR S
C A R B ON MON OX I D E A L A R MS
A merican Sensors also offers a complete line of C arbon Monoxide
A larms including :
C O800 -
Plug-In C arbon Monoxide A larm
C O810 -
120 Volt A C H ardwire C arbon Monoxide A larm
C O900 -
Plug-In C arbon Monoxide A larm with Battery Back-
U p
C O910 -
Plug-In C arbon Monoxide A larm with Digital LED
Display
C O920 -
Plug-In C arbon Monoxide A larm with Digital LED
and Back-U p Power Source
C O1100 - Battery Powered C arbon Monoxide A larm for Table
Top, Travel or Wall Mount
120 VAC -IONIZ A T ION
SMOKE A LA RM
M OD E L
SA 360
R E AD CAR E F U L LY AN D SAVE .
T his manual contains important information.
A copy of this manual must be left with the end user.
2502-2509 ( R EV-1)