STFV.425238.034-AU-UM rev. 14
PROGRAMMING
The "Prog." button on the device is used for initializing the device on to the system.
Please refer to the translator manual for full instructions on how to add a device to
the system. The device can also be initialized using the "Ekho Configuration"
software.
INSTALLATION
In order to install the device, the mounting base
should be fixed to the ceiling, the sensor can then be
inserted into the base by rotating the sensor until it
clips into the base.
Preferably, the device should be installed away from
metallic objects, doors, and power lines, as they can
cause the communication distance to drop. It is also
important to avoid installing the device near electronic
and computer equipment in order to protect it from
potential electromagnetic interference.
INDICATION
The device has a LED, which indicates its state according to the following:
LED indication
No indication or green flashes
Yellow flashes every 4 seconds
Red flashes every 2 seconds
EK-WL8-H/AU
WIRELESS HEAT SENSOR
10.08.2020
Device's state
Standby mode
Fault state – low battery or thermal sensor
fault
Fire alarm
Page 3 from 6