Ekinex EK-GD1-TP-4-HV Manuel de configuration et d'installation - Page 2
Parcourez en ligne ou téléchargez le pdf Manuel de configuration et d'installation pour {nom_de_la_catégorie} Ekinex EK-GD1-TP-4-HV. Ekinex EK-GD1-TP-4-HV 6 pages. Vac 4-channel phase cut dimmers
Control, signaling and connection elements
The device is equipped with a spring clamp for connec-
ting the output loads on 4 channels and the 90 - 230 Vac
input power supply (1). There is also a signaling LED for
the presence of the power supply (2), a button and LED
for each channel (3), for local on / off test in case of KNX
bus absence, a terminal for connecting the KNX bus (4),
a KNX programming button (6) with LED (5).
To carry out the local on/off test, briefly pressing the but-
ton turns the connected load on or off, while pressing it
for at least 2 seconds makes the load flash approximately
every 1 s.
1
2
Power
3
EK-GD1-TP-4-HV
Dimmer KNX 90-230V~ 50/60 Hz
Out: 4x 200W
1
2
4
EK-GD1-TP-4-HV
Nr.
Label
Connection
1
-
Power supply and loads clamps
2
Power
Signalling LED
3
x
LED and channel x (x = 1,2,3,4) button
4
-
KNX bus terminal
5
-
Programming LED
6
-
KNX Programming button
The terminal diagram for power supply and loads is as
follows.
1
2
3
4
5
6
1
2
3
Label
Connection
L
AC input - Live
N
AC input - Neutral
COM
Channel x (x=1,2,3,4) AC output - Neutral
x
Channel x (x=1,2,3,4) AC output - Live
6
3
4
5
7
8
9
10
11
12
N
L
N
L
4
Montaggio
The devices have degree of protection IP00 (IP20 inside
a wall-mounting box or electrical panel).and are therefore
suitable for use in dry interior rooms.
Before removing the device, make sure that inputs, ou-
tputs, and the AC power supply have been disconnected.
When assembling, make sure to leave only the front pa-
nel accessible; all other sides must not be accessible. For
the mounting proceed as follows:
• with the aid of a tool bring the locking device in the fully
lowered position (a);
• place the upper edge of the rear inner profile on the
upper edge of the rail (b);
• rotate the device towards the rail (c);
• push the locking device upward until it stops (d).
a
c
Before removing the device, be sure that inputs, outputs,
and the input power supply have been disconnected. Use
a screwdriver to slide down the locking device and remo-
ve the device from the rail.
i
Note. When mounting the device in boards and ca-
binets it shall be provided the necessary ventilation
so that the temperature can be kept within the ope-
rating range of the device.
Setup and installation
The steps to setup the device are as follows:
1. Connect the loads to the AC OUT (
of the device
2. Connect the KNX bus to the corresponding terminal of
the device
3. Connect the 90 - 230 Vac power supply to the AC IN (L,
N) terminals of the device
2
b
d
-x, N) terminals