Ekinex EK-CLM-GAG Manuel - Page 3
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Ekinex EK-CLM-GAG. Ekinex EK-CLM-GAG 4 pages. Movement sensor with 180 detection area
Mounting
The device has degree of protection IP20, and is therefo-
re suitable for use in dry interior rooms. The device has to
be installed with the metallic support and the screws (in-
cluded in the delivery) on a wall box with 60 mm distance
between fixing holes. Previously connect the bus terminal
block to the bus cable (see: "Connection of the KNX bus
line") and enter it in its slot on the rear of the device. At
this point it is recommended to carry out the commissio-
ning of the device (see "Commissioning") or at least the
download of the physical address. Eventually snap the
cover with lens on the device.
Connection of the KNX bus line
The connection of the KNX bus line is made with the ter-
minal block (8) included in delivery and inserted into the
slot of the housing.
Characteristics of the KNX terminal block
• spring clamping of conductors
• 4 seats for conductors for each polarity
• terminal suitable for KNX bus cable with single-wire
conductors and diameter between 0.6 and 0.8 mm
• recommended wire stripping approx. 5 mm
• color codification: red = + (positive) bus conductor,
black = - (negative) bus conductor
Warning! The electrical connection of the device
!
can be carried out only by qualified personnel. The
incorrect installation may result in electric shock or
fire. Before making the electrical connections, make
sure the power supply has been turned off.
+
KNX
bus
-
Warning! In order to supply the KNX bus lines use
!
only KNX bus power supplies (e.g. ekinex EK-AB1-
TP or EK-AG1-TP). The use of other power supplies
can compromise the communication and damage
the devices connected to the bus.
Configuration and commissioning
Configuration and commissioning of the device require
the use of the ETS
(Engineering Tool Software) program
®
V3 or later releases. These activities must be carried out
according to the design of the building automation system
done by a qualified planner.
i
Note. The configuration and commissioning of KNX
devices require specialized skills. To acquire these
skills, you should attend the workshops at KNX cer-
tified training centers.
Configuration
For the configuration of the device parameters the corre-
sponding application program or the whole ekinex
duct database must be loaded in the ETS program. For
detailed information on configuration options, refer to the
application manual of the device available on the website
www.ekinex.com.
Application pro-
Code
gram
(## = release)
EK-SM2-TP
APEKSM2TP##.vd4
Commissioning
For commissioning the device the following activities are
required:
• make the electrical connections as described above;
• turn on the bus power supply;
• switch the device operation to the programming mode
by pressing the programming pushbutton located on
the front side of the housing. In this mode of operation,
the programming LED is turned on;
• download into the device the physical address and the
configuration with the ETS
At the end of the download the operation of the device
automatically returns to normal mode; in this mode the
programming LED is turned off. Now the bus device is
programmed and ready for use.
i
Note. After the connection to the KNX bus it is ne-
cessary to wait approximately a minute before the
sensore reaches a stable functioning condition.
Troubleshooting
Error
Cause / action
- the twilight value is too high
The load does
- check the lighting devices
not switch
- check the power supply / the protections
- check if in the detection area there are potential
causes of unjustified activation, such as presence
The sensor is
of pets, heating sources, etc.
activated without
- check the distance from the lighting devices
reason / the light
(heating reflexion or direct influence of the light)
never switches
- the sensisbility of the sensor is too high; reduce
off
the sensibility of the detection area (1...10) with
ETS
The light switches
- twilight regulation is set to a too high value; set
on during the
a lower value with ETS
daytime
Dimensions [mm]
3
pro-
®
Communica-
Group ad-
tion objects
dresses
(max nr.)
(max nr.)
19
254
program.
®
70