AMES A200 Fiche technique - Page 4

Parcourez en ligne ou téléchargez le pdf Fiche technique pour {nom_de_la_catégorie} AMES A200. AMES A200 4 pages. Pressure vacuum breaker

AMES A200 Fiche technique
Ames Model A200
Service, Replacement Parts and Maintenance
A200 REPAIR KITS
Check Kit: Include Check disc assembly (disc and disc
holder), Bonnet, O-ring and Spring.
Vent Float Kits: Includes Float vent disc assembly, (vent
float, spring) and Bonnet O-ring.
Bonnet Assembly Kits: Include Bonnet, Bonnet O-ring
an Vent Spring.
Rubber Parts Kits: Include Vent disc, Check disc and
Bonnet O-ring.
Seal Kits: Include Seat, Seat O-ring and Bonnet O-ring.
CALIFORNIA PROPOSITION 65 WARNING
This product contains lead, a chemical known to the State of California to cause birth defects or other reproductive harm.
(Plumber: California law requires that this warning be given to the consumer.)
CONSUMER INFORMATION ABOUT CALIFORNIA PROPOSITION 65 WARNING
All faucets and products made of leaded brass alloys, even those that comply with U.S. Environmental Protection Agency
regulations, contribute small amounts of lead to water that is allowed to stand in contact with the brass. This product
complies with all E.P.A. regulations regarding the amount of lead used in plumbing brass and solder. The amount of lead
contributed by any faucet/product is highest when the faucet/product is new.
The following steps will reduce potential exposure to lead from faucets and other parts of the plumbing system:
Always run the water for a few seconds prior to use for drinking or cooking.
Use only cold water for drinking or cooking.
If you wish to flush the entire plumbing system of water that has been standing
in the pipes or other fittings, run the cold water until the temperature of the
water drops, indicating water coming from the outside main.
If you are concerned about lead in your water, have your water tested by an
EPA-certified laboratory in your area.
Sizes 3/4" to 2"
Internal parts can be removed, repaired or inspected
without removing the valve from the piping.
Disassembly:
1. Shut off the supply pressure and drain the valve.
2. Remove the two hood screws and the hood.
3. Place a wrench on the parallel flats of bonnet and stem
assembly. Turn counter clockwise and remove.
4. Remove the vent assembly.
5. Press down on the spring retainer and disengage it from the
retaining lugs. Then turn 90º and remove.
6. Remove the spring retainer and spring. Note that the large
diameter of the spring is down on the guide assembly.
7. Remove the check disc holder and guide assembly.
8. Disassemble the check disc holder assembly.
Reassembly:
Reassemble in the reverse order utilizing the new parts from
the repair kit.
Note: Ames assemblies require minimum maintenance. All assemblies
must be retested once maintenance has been performed prior to use.
Freeze Protection Guidelines:
Purging of a PVB Assembly with Pressurized Air:
1. Close main shut-off valve.
2. Open upstream drain, test cocks and isolation ball valves to
depressurize line.
3. Purge with pressurized line
4. Leave test cocks and isolation ball valve handles in 45º
angle to drain ball valves and prevent casting damage
Limited Warranty
(Full description of limited warranty is found in Ames
Product catalogue.)
This Ames warranty is expressly in lieu of any other warranties, expressed or
implied including without limitation, warranties of MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE. Ames shall not be responsible for
any incidental or consequential damages including without limitation, damages
or other costs resulting from labor charges, delays, vandalism, negligence, foul-
ing caused by foreign material, damage from adverse water conditions, chemi-
cals, or any other circumstances over which Ames has no control.
No statement, representation, agreement or understanding, oral or written,
made by agent, by an authorized Ames dealer, an Ames representative or em-
ployee which is not contained in this limited warranty will be recognized or en-
forceable or binding upon Ames Company, Inc. Only a written statement signed
by and officer of Ames may modify this limited warranty.
Any action for breach of any Ames Warranty must be commenced within one
(1) year after date on which cause of action occurred.