4. Touch the SET key (or do not operate for 15 seconds), the display will show the
label "SP"
5. Touch the UP or DOWN key to select a parameter to modify
6. Touch the SET key, the display will show the actual value
7. Touch the UP or DOWN key within 15 seconds to set the value
8. Touch the SET key (or do not operate for 15 seconds)
9. Touch the SET key for 4 seconds (or do not operate for 60 seconds, or press the
OFF key) to exit the procedure
e
nable temperatUre deCimal point
Follow the parameters setting procedure
Reach parameter "P1"
0=no 1=yes (default: 1)
Exit the procedure
C
hange temperatUre Unit of measUre
Follow the parameters setting procedure
Reach parameter "P2"
0=°C 1=°F (default: 0)
Exit the procedure
s
et a Cabinet probe offset
Follow the parameters setting procedure
Reach parameter "CA1".
Min...Max values are -25...+25 °C/°F
Exit the procedure
s
h
/ l
et an
igh
ow temperatUre alarm
The EVCO electronic thermostat is equipped with an internal buzzer and high / low
temperature alarms can be set. As there is not real time clock, back up battery and
memory, alarms are active only with power connected and are not recorded.
To set high / low temperature alarms;
follow the parameters setting procedure
reach parameter "A2", low temperature alarm type
- 0=disabled, 1=relative to set point, 2= absolute (default is 0)
- touch UP or DOWN to select a value and touch SET key to set it
reach parameter "A1", threshold for low temperature alarm
- Min...Max values are -99...+99 °C/°F
- touch UP or DOWN to select a value and touch SET key to set it
reach parameter "A5", high temperature alarm type
- 0=disabled, 1=relative to set point, 2= absolute (default is 0)
- touch UP or DOWN to select a value and touch SET key to set it
reach parameter "A4", threshold for high temperature alarm
- Min...Max values are -99...+99 °C/°F
- touch UP or DOWN to select a value and touch SET key to set it
(