Testing
2.3.1. For the period of testing, please disconnect executive outputs of CIE and appliances that control the fixed fire
suppression system. Notify the proper authorities that the system is undergoing maintenance.
2.3.2. By means of the network controller arm the CIE input the manual call point is connected to.
2.3.3. Activate the manual call point by pressing the operating element. The IPR 513-3M shall enter the Fire2 Alarm
condition: observe LED's showing solid light and network controller's displaying the Fire2 Alarm message from the input the call
point is connected to.
2.3.4. Reposition the operating element to the quiescent mode by inserting the housing key. Ensure the call point LED starts
flashing once per 4 s. Then, with the help of the network controller issue a comand to reset the alarm on the CIE input the call point
is connected to. If no Fire2 Alarm message is registered by the network controller or the call point's LED operates in a way which
differs from the one stated in this manual, the manual call point is unhealthy and should be replaced.
2.3.5. Perform steps 2.3.2 – 2.3.4 at least triply.
2.3.6. When testing is completed, make sure that the manual call point is ready for normal operation. Reconnect control and
indicating equipment and control appliances with fixed fire suppression equipment and notify the proper authorities that the system
is back in normal operation.
Test the operability of the manual call point at least once per three months.
All the equipment used in testing must be known functioning!
The manual call point shall be maintained throughout a year by specialists whose electrical safety level is not lower than 3
per the schedule presented below.
Checking conditions of the call point housing, ensuring that the manual call
point is fastened properly and its connecting wires and contact joints are in
good conditions
Removing dust, debris, and corrosion from the contact joints and housing
Testing operability of the manual call point in line with instructions of
Section 2.3 of this manual
4.1. The expected lifetime of the IPR 513-3M is 10 years.
4.2. The warranty period is 18 months since putting the product into operation but no more than 24 months from the
manufacturer's date of production.
4.3. In case of any issue related to setting or operation of the product, please contact the technical support: +7 (495) 775-71-55
or e-mail
4.4. For warranty return of the product, a reclamation report describing the failure shall be applied to it.
Claims shall be submitted to the following address:
NVP BOLID, #4 Pionerskaya Str., Korolyov, Moscow Region, 141070, Russia
Tel./fax: +7 (495) 775-71-55 (PBX), 777-40-20, 516-93-72.
E-mail: [email protected], Technical Support: [email protected],
5.1
IPR 513-3M meets the requirements of "Technical Regulations on Fire Safety Requirements" (Federal Law No.123-FZ of
July 22, 2008) and is covered by Conformity Certificate No. C-RU.ЧС13.В.00845.
5.2
IPR 513-3M meets the requirements of Technical Regulations of Custom Union TR CU 020/2011 "Electromagnetic
Compatibility of Technical Equipment" and is covered by Conformity Declaration ЕАЭС № RU Д-RU.НР15.В.06593/20.
5.3
IPR 513-3M meets the requirements of Technical Regulations TR EAEU 037/2016 "On the restriction of the use of
hazardous substances in electronic and radio electronic equipment" and is covered by Conformity Declaration ЕАЭС № RU Д-
RU.РА01.В.82301/19.
5.4
The production of IPR 513-3M is awarded with Conformity Certificate GOST R ISO 9001. The Certificate is available on
the website
https://bolid.ru
IPR 513-3M resettable manual call points (serial numbers are located on labels inside their housings) are accepted in line with
mandatory requirements of national standards and applicable technical documentation, approved as ready for use, and packaged by
the Bolid Company.
QCD ________________________________
4 MANUFACTURER'S WARRANTY
5 CERTIFICATION INFORMATION
in the section ABOUT.
6 ACCEPTANCE AND PACKAGING CERTIFICATE
Responsible for acceptance and packaging
Name
3 MAINTENANCE
https://bolid.ru.
________________________
2
Quarter I
Quarter II Quarter III Quarter IV
Date/Month/Year
rd
and as