bolid IPR 513-3M Manuel de conversation - Page 5

Parcourez en ligne ou téléchargez le pdf Manuel de conversation pour {nom_de_la_catégorie} bolid IPR 513-3M. bolid IPR 513-3M 15 pages.
Également pour bolid IPR 513-3M : Manuel d'instruction (2 pages)

bolid IPR 513-3M Manuel de conversation
1.2

Specifications

1.2.1 Max power supply voltage
1.2.2 Rated power supply voltage
1.2.3 Current consumption in the quiescent mode
1.2.4 Switching current
1.2.5 Maximum active resistance of alarm loop wires
1.2.6 Minimum insulation resistance between alarm loop wires
1.2.7 Enclosure protection degree as per GOST 14254-2015
1.2.8 Resistance to mechanical exposure as per OST 25 1099-83
1.2.9 Vibration exposure:
- Frequency range
- Max acceleration
1.2.10 Environment category as per OST 25 1099-83
1.2.11 Operating temperature range
1.2.12 Relative air humidity
1.2.13 Weight
1.2.14 Housing dimensions
1.2.15 Non-stop operation
1.2.16 MTBF in the quiescent mode
1.2.17 Survival probability
1.2.18 Expected lifetime
1.2.19 As to immunity to electromagnetic interference, the IPR 513-3M meets the requirements of Test
Severity Level III as per the relevant standards listed in Annex B to GOST R 53325-2012.
1.2.20 The IPR 513-3M passes the industrial interference standards prescribed for Class B equipment per
GOST R 30805.22.
5
Parameter
Table 1.2.1
Value
30 V
24 V
50 uA max
25 mA max
100 Ohm
50K Ohm
IP40
Arrangement Category III
1-35 Hz;
0.5g;
О3
Minus 30 to + 55°С
Up to 93 % at +40°С
0.15 kg max
95 × 91 × 34 mm max
24/7
80,000 hours min
0.98758
10 years